ENGLISH-33
03
ADV
ANCED
OPER
ATION
Installation/Service mode
•
'NONE' will be displayed for the menu that setting modes don't support. In some cases, the setting may not be
possible or it may not be applied though it is set on the unit.
•
If communication initialization is needed after saving the setting, the system will reset automatically and
communication will be initialized.
NOTE
Main
Menu
Sub
Menu
Function
SEG
number
Default
Range
Unit
1
1
Wired remote
controller’s option
function set /Check
1
Cooling support Y / N
1
0
0 – Both cooling & heating
1 – Heating Only
-
Selecting the standard
temperature of cooling and
heating
2
0
0-Water Outlet temperature
1-Indoor temperature
-
Selecting a standard sensor
of indoor temperature
3
0
0-Temperature sensor of wired
remote controller 1-External
temperature sensor
-
Selecting Master/Slave
4
0
0-Master, 1-Slave
-
2
Wired
remotecontroller’s
option function set /
Check 2
Checking current sensor
temperature value
123
0
-9~40˚C
-
3
Setting compensation
temperature value
123
0
-9.9~9.9˚C
0.1 ˚C
4
Checking the
number of
connected devices
The number of connected
device
1,2
0
0~16
1
5
Setting desired temperature unit (Available only
when the temperature display is °C)
1
1
0-1˚C, 1-0.5˚C, 2-0.1˚C
-
0
Reset to option setting default value of
wiredremote controller
1
0
0-Disuse, 1-Reset
-
2
1
Checking Micom code of wired remote controller 1234, 4
-
Micom code
-
2
Checking version information of wired remote
controller
1234, 34
-
Revision date
-
3 *1)
1
Setting CONTROL
KIT option
CONTROL KIT address Set/
Check
1234
-
*2)
2
Basic Option Set/Check
1234, 12
-
Option code
3
Install Option Set/Check
1234, 12
-
Option code
4
Install(2) Option Set/Check 1234, 12
-
Option code
4
1
View Master Set/
Check
CONTROL KIT View Master
Set/Check
1234, 34
-
Address
2
Master CONTROL KIT
Set/Check
Check the Master CONTROL
KIT address
1234, 34
-
Address
3
Master CONTROL KIT Set
1
-
0-Disuse, 1-Use, 2-Reset
0
1
Reset
Wired remote controller
factory Reset
1
0
0-Disuse, 1-Reset
-
2
Power Master Reset
1
0
0-Disuse, 1-Reset
-
3
Addressing Reset(Outdoor
unit Reset)
1
0
0-Disuse, 1-Reset
-
*1) When entering the main menu 3, set and check the unit address and then move to the sub menu.
The unit address will be displayed by blinking SEG 34 (Device ID) and SEG 1234 (Control Layer, Set Layer address).
*2) 1. Reservation No. 1 display, Main address setting and checking: Range of current main address (SEG 1, 2) and main
address setting: 0x00 ~ 0x4F (hexadecimal)
2. Reservation No. 2 display, Group address setting and checking: Range of current group address (SEG 1, 2) and group
address setting: 0x00 ~ 0xFE (hexadecimal)