ENGLISH-38
Troubleshooting
Water pump &flow S/W
Display
Explanation
Flow S/W OFF error
• In case of flow S/W OFF in 30 sec during water pump signal is ON(Starting)
• In case of flow S/W OFF in 15 sec during water pump signal is ON (After starting)
Flow S/W ON error
• In case of flow S/W ON in 10min during water pump signal is OFF
Tw3
Tw2
Tw1
Water Out
Water In
E911
f
f
Water pump ON ( Flow S/W off )
Water flow > 12LPM (AE160JNYDEH, AE160JNYDGH)
Water flow > 7LPM (AE090JNYDEH, AE090JNYDGH)
f
f
Water pump ON ( Flow S/W off ) : NOT enough water flow
Water flow < 12LPM (AE160JNYDEH, AE160JNYDGH)
Water flow < 7LPM (AE090JNYDEH, AE090JNYDGH)
E912
f
f
Water pump OFF ( Flow S/W on )