ENGLISH-36
Troubleshooting
If the unit has some problem to work properly, the LED on hydro unit will flash and some error codes will be displayed on the
controller .
The following table described the explanation of error codes on the LCD display .
Thermistor
f
f
Check its resistance . 10kohm@25 °C (Hydro unit), 200kohm@25 °C (DHW Tank, Solar)
f
f
Check its location as shown at the diagram .
f
f
Check its contact status with pipe .
f
f
Final solution is to change parts
Display
Explanation
Wired remote controller thermistor SHORT or OPEN
Water Inlet thermistor SHORT or OPEN
PHE Outlet thermistor SHORT or OPEN
Water Outlet thermistor SHORT or OPEN
Water TANK thermistor SHORT or OPEN
Mixing Valve thermistor SHORT or OPEN
Tw3
Tw2
Tw1
E903
Water Outlet
thermistor
Water Out
Water In
Water inlet
E901
Wired remote
controller
thermistor
E653
Water tank
thermistor
E904
E903
OTHERS