36
Installation Procedure
Ins
tallation Pr
oc
edur
e
English
Step 15 External Static Pressure (ESP) setting for phase control motor
With its phase control motor, you can adjust the indoor unit fan speed depending on the installation condition. If the
external static pressure is high so that the duct becomes longer or if the external static pressure is low so that the
duct becomes shorter, adjust the fan speed by referring the following table.
Model
AE022MNLDEH
AE028MNLDEH
AE036MNLDEH
AE056MNLDEH
Static Pressure(mmAq)
Option code for indoor unit
0
010054-125A80-
201616-331110
010054-125AE2-
201C1C-331110
010054-125E35-
202424-331110
010054-125AC1-
203838-331110
1
010054-125AC3-
201616-331110
010054-125E15-
201C1C-331110
010054-125E68-
202424-331110
_
2
_
_
_
010054-125E34-
203838-331110
3
010054-125E08-
201616-331110
010054-125E7A-
201C1C-331110
010054-125ECD-
202424-331110
_
4
_
_
_
010054-125EF9-
203838-331110
Model
AM045HNMPKH
AM056HNMPKH
AM071HNMPKH
Static Pressure(mmAq)
Option code for indoor unit
0≤ SP ≤3
010054-1C50D1-
202D2D-331204
010054-1C50F1-
203838-331203
010054-1C548D-
204747-331201
3< SP ≤6
010054-1C5453-
202D2D-331204
010054-1C5447-
203838-331203
010054-1C55E1-
204747-331201
6< SP ≤9
010054-1C54C7-
202D2D-331204
010054-1C54AB-
203838-331203
010054-1C5935-
204747-331201
9< SP ≤12
010054-1C583B-
202D2D-331204
010054-1C581F-
203838-331203
010054-1C5989-
204747-331201
12< SP ≤15
010054-1C58AF-
202D2D-331204
010054-1C5973-
203838-331203
010054-1C59DF-
204747-331201
Model
AM090HNMPKH
Static Pressure(mmAq)
Option code for indoor unit
0≤SP≤4
010054-1C546D-205A5A-331212
4<SP≤8
010054-1C55E3-205A5A-331212
8<SP≤12
010054-1C5969-205A5A-331212
12<SP≤15
010054-1C59CD-205A5A-331212
NOTE
•
represents E. S. P(External Static Pressure) range of factory setting.
You don’t have to adjust the fan speed separately if the external static pressure of the installation place is in
.
When it is out of
, input the appropriate option code.
•
If you input the inappropriate option code, error may occur or the air conditioner is out of order. The option code
must be inputted correctly by the installation specialist or service agent.