Please refer to the EEV step table below for the system (for heating) at stop.
Indication
0
2
3
4
5
6
7
8
9
A
B
Stopped
Unit's
EEV step
Wall MountedWith EEV
A
Step
100
90
100 110 120 130 160 200 250 300 400
B
Step
125
160
160 160 160 160 160 200 250 300 400
Other Indoor Units except for
wall mounted with EEV
Default
No Function
(*4)
When the following 2 or 3 is used as external heater On/Off signal, the signal for monitoring external contact
control will not be output.
2: Fan is turned on continually when the external heater is turned on,
3: Fan is turned off when the external heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option,install the
Mode Select switch
(MCM-C200) on the outdoor unit and
fix it as
Cool
mode.·
•
If Fan is set to off for cooling only indoor unit by setting the SEG9=3 or SEG15=3, you need to use an external sensor
or wired remote control sensor to detect indoor temperature exactly.
(*5)
Default setting value
– 4Way Cassette, Mini 4Way Cassette: 5 °C
– Other indoor units: 2 °C
(*6)
This function can be applied to 4 Way Cassette and Mini 4 Way Cassette only. If the air conditioner operates the
heating mode immediately after finishing the cooling mode, the condensated water in the drain pan becomes
water vapor by the heat of the indoor unit heat exchanger. Since the water vapor might be condensed on the
indoor unit, which may fall into a living space, use this function to get rid of the water vapor out of the indoor
unit by operating the fan (for maximum 20 minutes) even when the indoor unit is turned off after cooling mode is
turned to heating mode.