Setting an indoor unit installation option (suitable for the condition of each installation location)
1
Check whether power is supplied or not.
– When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2
Set the installation option according to the installation condition of an air conditioner.
– The default setting of an indoor unit installation option is 020010-100000- 200000-300000.
– Individual control of a remote control(SEG20) is the function that controls an indoor unit individually when
there is more than one indoor unit.
3
Set the indoor unit option by wireless remote control.
02 series installation option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
2
-
External room
temperature sensor /
Minimizing fan operation
when thermostat is off
Central control
FAN RPM
compensation
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
-
-
-
EEV Step when
heating stops
-
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
External control
External control output /
External heater On or Off signal
S-Plasma ion
Buzzer
Number of
hours using
filter
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
Individual
control of a
remote control
Heating setting compensation
/ Removing condensated water
in heating mode
EEV Step of stopped unit
during oil return/defrost
mode
-
-
• When setting the option other than above SEG values, the option will be set as “0”.
• SEG5 central control option is basically set as 1 (Use), so you don’t need to set the central control option
additionally.
However, if the central control is not connected but it doesn’t indicate an error message, you need to set the central control option as 0
(Disuse) to exclude the indoor unit from the central control.
• The external output of SEG15 is generated by MIM-B14 connection. (Refer to the manual of MIM-B14.)