Emergency Temperature Output (ETO) function
CAUTION
ŷ
In order to deploy the ETO function, the MIM-B14, an external contact interface module, must be installed in each
indoor unit.
– The ETO is a concept of emergency operation of indoor units. If the indoor unit 1 (main indoor unit) stops because
of an error, the indoor unit 2 (sub indoor unit) starts to operate.
– Basically, the indoor unit 2 operates in the previous mode. [For the first time operation, it starts in 24 °C Auto mode.]
– To set more detailed operation conditions for the indoor unit 2, use the S-net Pro.
Setting up the ETO
Communication between
indoor and outdoor units
(F1 and F2)
External contact
interface module
MIM-B14
Error output port (1, 2)
Contact input port (5, 6)
Main indoor unit
Sub indoor unit
1
Main indoor unit
– Disable the external contact control (Default).
– Connect the S-net pro2 to F1 and F2.
– Enable the ETO function and set the temperature and time.
2
Sub indoor unit
– (Required) Enable the external contact control (with the installation option SEG14 - Reverse Control).
– Connect the S-net pro2 to F1 and F2.
– Enable the entrance control and set the mode, set temperature, and fan speed.
[Master]
[Slave]