32
Installation Procedure
Ins
tallation Pr
oc
edur
e
English
CAUTION
ŷ
The main address must be set to a value in the range
0 to 15. If you set other values, communication error
will occur.
ŷ
If any of SEG5 and SEG6 is set to a value in the range
A to F, the main address of the indoor unit does not
change.
ŷ
If SEG3 is set to 0, the indoor unit maintains the
existing main address even if SEG6 is set to a new
value.
ŷ
If SEG9 is set 0, the indoor unit maintains the existing
RMC address even if SEG11 and SEG12 are set to new
values.
Setting the installation options in a batch
Option No. for an indoor unit address:
02XXXX-1XXXXX-2XXXXX-3XXXXX
1
Make sure that the power is supplied to the indoor
unit. If the indoor unit is not plugged in, it must
include a power supply.
Indoor unit
F1
F2
LN
2
Set the installation options of indoor units, by
referring to the following table and by following the
steps in
Common steps for setting the addresses and
options
on page
20
.
ŷ
The installation options of indoor units are set to
020000-100000-200000-300000 by default.
ŷ
The SEG20 option, Individual control with remote
control, allows you to control multiple indoor units
individually by using the remote control.
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Function
Page
Mode
Reserved
Use of external
temperature sensor
Use of central
control
Compensation of
the fan RPM
Indication
and details
Indication
Details Indication
Details
Indication
Details
Indication
Details
Indication
Details
0
2
0
Disuse
0
Disuse
0
Disuse
(recessed
installation)
1
High-
ceiling
mode
(recessed
installation)
1
Use
1
Use
4
Disuse
(exposed
installation)
5
High-
ceiling
mode
(exposed
installation)
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Function
Page
Use of drain pump
Reserved
Reserved
Reserved
Reserved
Indication
and details
Indication
Details Indication
Details
1
0
Disuse
1
Use
2
Use with 3 minute
delay
Содержание AC100RN4PKG
Страница 38: ...This appliance is filled with R 32 ...