5 .  Purge the air from the system using vacuum pump for about 10 minutes .

f

f

Close the valve of the low pressure side of manifold gauge clockwise .

f

f

Make sure that pressure gauge shows -0 .1 MPa(-76cmHg) after about 10 
minutes . This procedure is very important to avoid a gas leak . 

f

f

Turn off the vacuum pump . 

f

f

Remove the hose of the low pressure side of manifold gauge .

6 .  Set valve cork of both liquid side and gas side of packed valve to the open 

position .

7 .  Mount the valve stem nuts and the service port cap to the valve, and tighten 

them at the torque of 158 .8 lbf•in with a torque wrench .

8 .  Check for gas leakage .

f

f

At this time, especially check for gas leakage from the 3-way valve’s stem 
nuts(A port), and from the service port cap .

B(liquid)

A(gas)

•  Connect the indoor and outdoor units using pipes with flared connections (not supplied) . For the lines, use 

insulated, unwelded, degreased and deoxidized copper pipe, (Cu DHP type to ISO 1337 or UNI EN 12735-1), 
suitable for operating pressures of at least 4200 kPa and for a burst pressure of at least 20700 kPa . Copper pipe 
for hydro-sanitary applications is completely unsuitable .

•  For sizing and limits (height difference, line length, max . bends, refrigerant charge, etc .) see “Connecting 

refrigerant pipe section” .

CAUTION

Connecting up and removing air in the circuit

4way Outdoor_북미향_IM_EN_05138A-00.indd   20

2014-12-08   오후 3:12:47

Содержание AC024JXADCHA

Страница 1: ...SUNG ELECTRONICS CO LTD 107 Hanamsandan 6beon ro Gwangsan gu Gwangju si Korea 506 723 Samsung Electronics UK Ltd Euro QA Lab Blackbushe Business Park SaxonyWay Yateley Hampshire GU46 6GG United Kingdom 4way Outdoor_북미향_IM_EN_05138A 00 indd 32 2014 12 08 오후 3 12 49 ...

Страница 2: ...AC048JXADCHA Air Conditioner installation manual imagine the possibilities Thank you for purchasing this Samsung product This manual is made with 100 recycled paper EN PT ES FR DB68 05138A 00 4way Outdoor_북미향_IM_EN_05138A 00 indd 33 2014 12 08 오후 3 12 49 ...

Страница 3: ...headset USB cable should not be disposed of with other household waste at the end of their working life To prevent possible harm to the environment or human health from uncontrolled waste disposal please separate these items from other types of waste and recycle them responsibly to promote the sustainable reuse of material resources Household users should contact either the retailer where they pur...

Страница 4: ... areas used for laundry f f Do not use the units if damaged If problems occur switch the unit off and disconnect it from the power supply f f In order to prevent electric shocks fires or injuries always stop the unit disable the protection switch and contact SAMSUNG s technical support if the unit produces smoke if the power cable is hot or damaged or if the unit is very noisy f f Always remember ...

Страница 5: ...other elevation system will NOT be considered part of the warranty and will be charged to the end customer f f If you operate the cooling operation of air conditioner in the condition that ambient temperature is lower than 23 F DB Dry bulb a wind baffle should be installed to protect the compressor of the outdoor unit Power supply line fuse or circuit breaker f f Always make sure that the power su...

Страница 6: ... outdoor unit by two 26 2 ft or longer wire ropes as shown at the figure To prevent from damage or scratches insert a piece of cloth between the outdoor unit and rope then move the unit The appearance of the unit may be different from the picture depending on the model Plate protection cloth Wire rope 4way Outdoor_북미향_IM_EN_05138A 00 indd 5 2014 12 08 오후 3 12 45 ...

Страница 7: ... outdoor unit so that the air flow is directed towards the open area f f Maintain sufficient clearance around the outdoor unit especially from a radio computer stereo system etc Fuse Outdoor Unit Stereo 5ftormore Indoor Unit Control Air Guide Duct This product is not provided by Samsung 3 3 ft or more 3 3 ft o r m o re 5 ft o r m o re 5ftormore 5 ft or more Fuse 8 inch 12 inch f f If the outdoor u...

Страница 8: ...protection wall and the outdoor unit for exhausted air to ventilate Protection wall Outdoor unit Sea breeze Sea Install the outdoor unit in a place where water can drain smoothly If you cannot find a place satisfying above conditions please contact manufacturer Make sure to clean the sea water and the dust on the outdoor unit heat exchanger and spread corrosion inhibitor on heat exchanger At least...

Страница 9: ...re 5 91 or more 23 62 or more 59 06 or more 78 74 or more When 3 sides of the outdoor unit are blocked by the wall The upper part of the outdoor unit and the air outlet is towards the wall 19 69 or more 11 81 or more 11 81 or more 59 06 or more The upper part of the outdoor unit and the air outlet is opposite the wall When front and rear side of the outdoor unit is towards the wall 4way Outdoor_북미...

Страница 10: ...e 59 06 or more 78 74 or more When 3 sides of the outdoor unit are blocked by the wall The upper part of the outdoor unit and the air outlet is towards the wall 19 69 or more 11 81 or more 11 81 or more 59 06 or more The upper part of the outdoor unit and the air outlet is opposite the wall When front and rear side of the outdoor unit is towards the wall 4way Outdoor_북미향_IM_EN_05138A 00 indd 9 201...

Страница 11: ...or more 23 62 or more 118 11 or more 7 87 or more 118 11 or more When front and rear side of the outdoor unit is towards the wall The units must be installed according to distances declared in order to permit accessibility from each side either to guarantee correct operation of maintenance or repairing products The unit s parts must be reachable and removable completely under safety condition for ...

Страница 12: ...d by the wall 11 81 or more 59 06 or more 23 62 or more 23 62 or more When front and rear side of the outdoor unit is towards the wall 59 06 or more 23 62 or more 118 11 or more 7 87 or more 118 11 or more When 3 sides of the outdoor unit are blocked by the wall 500 or more 500 or more 300 or more 300 or more The upper part of the outdoor unit and the air outlet is towards the wall 4way Outdoor_북미...

Страница 13: ...iling strength and waterproof the unit CAUTION Outdoor Unit Support Anchor bolt 0 79 inchOutdoor Unit Base Surface Outdoor Unit Support Designed to cut off residual vibration from outdoor unit to rack not supplied with product OUTDOOR UNIT INSTALLED ONTHEWALL BY RACK f f Ensure the wall will be able to suspend the weight of rack and outdoor unit f f Install the rack close to the column as much as ...

Страница 14: ...sing the CD connector and bushing During the unit installation make first refrigerant connections and then electrical connections If unit is uninstalled first disconnect electrical cables then refrigerant connections Connect the air conditioner to grounding system before performing the electrical connection When installing the unit you shouldn t use inter connection wire CAUTION In case of extendi...

Страница 15: ...oad Ampere MCA Minumum Circuit Ampere A MOP Maximum Overcurrent Protective Device A NOTE Between Indoor unit and Outdoor unit Connection Cable Specifications Common in use Power supply Communation Cable Power supply Max Min V IndoorPowerCable 1Φ 208 230V 60Hz 10 0 0039 in 3wires 0 0011 0 0023 in 2wires f f Power supply cords of parts of appliances for outdoor use shall not be lighter than polychlo...

Страница 16: ...ser If the unbalanced power is exceeded over 4 of supply rating the indoor unit is protected stopped and the error mode indicates To protect the product from water and possible shock you should keep the power cable and the connection cord of the indoor and outdoor units within ducts with appropriate IP rating and material selection for your application Ensure that main supply connection is made th...

Страница 17: ...trical wiring so that the front cover does not rise up when doing wiring work and attach the front cover securely Ground wire for the indoor unit and outdoor unit connection cable must be clamped to a soft copper tin plated eyelet terminal with M4 screw hole NOT SUPPLIEDWITH UNIT ACCESSORIES NOTE Connecting the cable 4way Outdoor_북미향_IM_EN_05138A 00 indd 16 2014 12 08 오후 3 12 46 ...

Страница 18: ... 4 3 8 0 2 0 007 12 5 1 2 13 1 2 38 1 1 2 8 4 1 3 16 0 4 0 015 0 0 1 8 0 07 8 3 16 22 7 8 13 1 2 43 1 11 16 8 4 1 3 16 50 0 07 8 3 16 22 7 8 0 3 0 011 13 5 1 2 0 5 0 019 0 2 0 007 11 4 7 16 0 3 0 011 17 5 11 16 14 9 16 50 2 8 4 1 3 16 0 4 0 015 0 0 1 8 0 07 70 0 10 8 3 16 24 1 0 4 0 015 17 5 11 16 0 5 0 019 0 4 0 015 13 3 1 2 0 4 0 015 18 5 3 4 20 3 4 51 2 8 4 1 3 16 0 4 0 015 0 0 2 0 0 078 f f Co...

Страница 19: ...for more than 3 4 in In case of using C1220T O Soft pipe for 3 4 in pipe may be broken which can result in an injury CAUTION Make at least one round It will reduce noise and vibration The appearance of the unit may be different from the diagram depending on the model After connecting pipes with knock out treatment plug the space Following the pipe connection make sure to proceed precisely to preve...

Страница 20: ...y pipe to the appropriate valve on the outdoor unit and tighten the flare nut 2 Referring to the illustration opposite tighten the flare nut on section B first manually and then with a torque wrench applying the following torque Outer Diameter D Torque lbf ft ø6 35 mm 1 4 10 3 13 3 ø9 52 mm 3 8 25 0 31 0 ø12 70 mm 1 2 36 1 45 0 ø15 88 mm 5 8 50 2 60 5 ø19 05 mm 3 4 73 8 88 5 3 Connect the charging...

Страница 21: ...ue wrench 8 Check for gas leakage f f At this time especially check for gas leakage from the 3 way valve s stem nuts A port and from the service port cap B liquid A gas Connect the indoor and outdoor units using pipes with flared connections not supplied For the lines use insulated unwelded degreased and deoxidized copper pipe Cu DHP type to ISO 1337 or UNI EN 12735 1 suitable for operating pressu...

Страница 22: ... mm 5 8 0 087 inch ø19 05 mm 3 4 0 087 inch 5 Check that the flaring is correct referring to the illustrations below for examples of incorrect flaring Uneven Thickness Cracked Damaged Surface Inclined Correct 6 Align the pipes and tighten the flare nuts first manually and then with a torque wrench applying the following torque Valve Flare nut Valve cap Pressure port cap Valve needle Pressure port ...

Страница 23: ...ons A and B Connecting the drain hose to the outdoor unit When using the air conditioner in the heating mode ice may accumulate During de icing defrost operation the condensed water must be drained off safely Consequently you must install a drain hose on the outdoor unit following the instructions below 1 Make space more than 3 15 inch between the bottom of the outdoor unit and the ground for inst...

Страница 24: ...favorable conditions use thicker one f f Insulator s heat resistance temperature should be more than 248 F Pipe Pipe size InsulationType Heating Cooling Remarks Standard Less than 86 F 85 High humidity over 86 F 85 EPDM NBR Liquid pipe 1 4 3 8 0 35 t 0 35 t Internal temperature is higher than 248 F 1 2 3 4 0 51 t 0 51 t Gas pipe 1 4 0 51 t 0 75 t 3 8 3 4 0 75 t 0 98 t f f When installing insulatio...

Страница 25: ...Check the leakage of refrigerant gas after tightening the cap Must use a spanner and wrench when you open tighten the stop valve CAUTION Interface module Installation Optional Accessories Interface module MIM B13D Interface module Interface module power cable Interface module communication cable Installation Manual Case Cable tie 1 Fix the case at with bolts on the side of the control box in the o...

Страница 26: ...n of the air conditioner Refer to this procedure when the unit is relocated Carry out the pump down procedure refer to the details of pump down Remove the power cord Disconnect the assembly cable from the indoor and outdoor units Remove the flare nut connecting the indoor unit and the pipe At this time cover the pipe of the indoor unit and the other pipe using a cap or vinyl plug to avoid foreign ...

Страница 27: ...to ground the air conditioner NOTE 3 Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit Terminal M4 PVC insulated green yellow wire To grounding screw Steel core Carbon plastic 1 6 ft 1 ft 4 Install a green yellow coloured grounding wire f f If the grounding wire is too short connect an extension lead in a mechanical way and wrapping it with insulating tape do...

Страница 28: ...nit check Outlet air temp Inlet air temp From 51 8 F to 57 2 F f f In heating mode the indoor fan motor can remain off to avoid cold air blown into conditioned space 5 How to reset the power supply of the outdoor unit and deactivate the eco mode standby mode f f Press K3 button over 1 sec to reset the power supply of the outdoor unit and deactivate the eco mode standby mode 6 View Mode When the K4...

Страница 29: ...Date Tens digit Date Unit digit After short push 1 E2P version Year Hex Month Hex Date Tens digit Date Unit digit Long push K4 Main micom ver short push 1 more Inv micom ver short push 1 more E2P ver 7 DIP switch option On default Off 1 2 3 4 ON Switch 1 Auto address Manual address Switch 2 Disable snow prevention control Enable snow prevention control Switch 3 Silence Mode option Switch 4 When sn...

Страница 30: ...d be installed to prevent the outdoor unit fan from operating in reverse way Make holes on the front side and attach the wind baffle using screws 22 6 inch 0 5 inch Partition When attaching the wind baffle using screws be careful that the screws do not damage the partition CAUTION Install outdoor units with the back surface facing wall side to eliminate the effects of external wind NOTE 4way Outdo...

Страница 31: ...heck Outdoor Cond E403 9 Protection of Outdoor Overload when Comp Stop Check Comp when it start E404 10 Discharge temperature of a compressor in an outdoor unit is overheated E416 11 Heating operation is not available since the outdoor air temperature is over 86 F Heating E440 Cooling operation is not available since the outdoor air temperature is lower than 5 F Cooling E441 12 Outdoor unit BLDC F...

Страница 32: ... 29 EEV orValve Close error Self diagnosis 1 Check if the service valve is open 2 Check for refrigerant leakage pipe connections heat exchanger and charge refrigerant if necessary 3 Check if there s any blockage on refrigerant cycle indoor unit outdoor unit 4 Check if additional refrigerant has been added after pipe extension E422 30 Outdoor EEPROM checksum error between MAIN and INVERTER Check Ou...

Отзывы: