Power Cable Specifications
f
f
The power cable is not supplied with air conditioner .
- Select the power supply cable in accordance with relevant local and national regulations .
- Wire size must comply with the applicable local and national code .
- Specifications for local wiring power cord and branch wiring are in compliance with local cord .
Model
Power source
RLA
FLA
MCA
MOP
AC018JXADCHA
208~230V/60Hz
6 .10 A
0 .13
14 .5 A
20 A
1 . RLA is based on AHRI 210/240 colling standard condition [Indoor temp . : 26 .7 °C / 80 °F(DB) / 19 .46 °C /
67 °F(WB), Outdoor temp . : 35 °C / 95 °F(DB)]
2 . Voltage tolerance is ± 10 % .
3 . Maxium allowable voltage between phases is 2 % .
Symbols
• RLA : Rated Load Ampere
• FLA : Full Load Ampere
• MCA : Minumum Circuit Ampere (A)
• MOP : Maximum Overcurrent Protective Device (A)
NOTE
Between Indoor unit and Outdoor unit Connection Cable Specifications(Common in use)
Power supply
Communation Cable
Power supply
Max/Min(V)
Indoor Power Cable
1Φ, 208~230V, 60Hz
±10%
0 .0039 in²
, 3wires
0 .0011~0 .0023 in², 2wires
f
f
Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible
cord . (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)
When installing the indoor unit in a computer room or net work room, use the
double shielded (Tape aluminum / polyester braid + copper ) cable of FROHH2R
type .
1-phase terminal block spec
AC power : M4 screw
Communication : M4 screw
1(L) 2(N)
N
L
11 .4
10 .1
L1
L2
POWER
10 .1
11 .4
Connecting the cable