Field settings to set, see user manual for a full list
2011 -2
low ambient setting for optimisation set to -5 in Scotland
2012 +15
high ambient temp for optimisation
2021 45C for u floor 50C for rads flow temperature in cold weather
2022 37C flow temperature in mild weather
2091 1
tells unit to look for a run signal on terminal B22
3011 1
tells unit it has a cylinder connected
3025 Max cylinder heating time, 50mins for 200ltr,
90mins for 300ltr
3032 Delay time before immersion heater starts, 30mins for 200ltr
, 60mins for 300ltr
3042 W
Wednesday day legionella happens (always use Wednesday)
#
3043 3am
time it happens
3044 60C legionella temp
# it is possible to scroll through the days & select every day, then legionella can be run daily
rather than weekly.
Cylinder timer
To avoid the cylinder heating being switched off we always add 2 on timers a day, one at 3-00
am and one at 15-00 pm. To insure the cylinder is hot 24 hours a day we don’t normally set
any off times.
Press
daily
button once, no 1 and on shows, press
grey set
, press up or down until the tap symbol
shows at the top of the screen with 2 dots
press
grey set,
adjust hours with up or down button to 3
am press
grey set
, minutes flash press set. Now
everything flashes press set (grey). No 2 appears do
the same again but for 15-00.
After everything is set no 3 will show. Press
cancel
delete
twice, the normal screen will show.
Daily will appear next to the time. The timer is active.
To
delete the timers
press daily 2 x the set schedule will show, press and hold cancel delete
for 5 seconds, keep doing this until no1 shows, press cancel delete 2 x and in the normal
screen daily will have disappeared.