D
Communication
NOTICE
The settings of configuration items D.2.1 and D.3.1 are only effective with the corresponding
interface board. See section 14.5.
Default
setting
Setting
D.1
General settings
D.1.1
-0
-1
Monitoring master
Off
On
D.1.1-0
QRY.TOUT
Query timeout <D.1.1-1>
[1 … 9999 s]
60 s
D.2
RS-232 interface
RS-232
interface
D.2.1
-0
-1
-2
-3
Protocol
Off
Automatic (9600, 8, N, 1)
SSP (9600, 8, N, 1)
Modbus RTU
D.2.1-1
STN
Station number <D.2.1-3>
[1 … 255]
1
BITRATE
Modbus Baud rate <D.2.1-3>
[300, 600, 1200, 2400,
4800, 9600, 19200, 38400,
57600, 115200 bit/s]
9600 bit/s
PARITY
Parity <D.2.1-3>
[0, 1]
0
STOPBIT
Stop bit <D.2.1-3>
1, 2
1
RSP.TOUT
Response timeout <D.2.1-3>
0.1 … 100.0 s
10.0 s
D.3
RS-485 interface
RS-485
interface
D.3.1
-0
-1
-2
-3
Protocol
Off
Automatic (9600, 8, N, 1)
SSP (9600, 8, N, 1)
Modbus RTU
D.3.1-1
STN
Station number <D.3.1-3>
[1 … 255]
1
BITRATE
Modbus Baud rate <D.3.1-3>
[300, 600, 1200, 2400,
4800, 9600, 19200, 38400,
57600, 115200 bit/s]
9600 bit/s
PARITY
Parity <D.3.1-3>
[0, 1]
0
STOPBIT
Stop bit <D.3.1-3>
1, 2
1
RSP.TOUT
Response timeout <D.3.1-3>
0.1 … 100.0 s
10.0 s
Appendix