Analog
output
AO2
O.2.1
-21
-22
-23
-24
-25
-26
-27
-28
-29
-30
-31
-32
-33
-34
-35
-36
-37
-38
-39
Assign source
[1] Actual ratio PVR
<M.1-2/-6>
[2] Input PV before filter
<M.1-3/-4/-5/-6, 2C.1.1.1
≠
0>
[2] Input PV after function generation
<M.1-3/-4/-5/-6, 2C.1.1.1
≠
0>
[2] Actual value PV0
<M.1-3/-4/-5/-6, 2C.1.1.1
≠
0>
[2] Input SPE before filter
<M.1-3/-4/-5/-6>
[2] Input SPE after function generation
<M.1-3/-4/-5/-6, 2C.1.2.1
≠
0>
[2] Input DV before filter
<M.1-3/-4/-5/-6, 2C.1.3.1
≠
0>
[2] Input DV after function generation
<M.1-3/-4/-5/-6, 2C.1.3.1
≠
0>
[2] Input TR before filter
<M.1-3/-4/-5/-6, 2C.1.4.1
≠
0>
[2] Input TR after function generation
<M.1-3/-4/-5/-6, 2C.1.4.1
≠
0>
[2] Input FB before filter
<M.1-3/-4/-5/-6, 2C.1.5.1
≠
0>
[2] Signal A
<M.1-3/-4/-5/-6, 2C.3.2.1
≠
0, 2C.3.2.3
≠
0>
[2] Signal B
<M.1-3/-4/-5/-6, 2C.3.2.3
≠
0>
[2] Set point SP0
<M.1-3/-4/-5/-6>
[2] Error /–e
<M.1-3/-4/-5/-6>
[2] Error signal e
<M.1-3/-4/-5/-6>
Output master controller YM
<M.1-3>
Y1
∗
Y2
∗
AO2.KM/100
<M.1-5/-6>
(100 – Y1)
∗
Y2
∗
AO2.KM/100
<M.1-5/-6>
AO2.FX
Constant output value <O.2.1-4>
[–10.0 ...110.0 %]
0.0 %
AO2.KM
Constant, mixing operation <O.2.1-38/-39>
[0.0 … 100.0]
1.0
O.2.2
-1
-2
-3
-4
Output signal <O.2.1
≠
0>
4–20 mA
0–20 mA
0–10 V
2–10 V
O.2.2-1
AO2.MIN
Minimum output value
[–10.0 ... 100.0 %]
0.0 %
AO2.MAX
Maximum output value
[0.0 ... 110.0 %]
100.0 %
O.2.3
-1
-2
Operating direction <O.2.1
≠
0>
Increasing
Decreasing
O.2.3-1
AO2.P1
Y value for AO2=AO2.MIN <O.2.3-1>
Y value for AO2=AO2.MAX <O.2.3-2>
[–10.0 ... 110.0 %]
0.0 %
The default value of
AO2.P1
is the same as
AO2.MIN
.
If
AO2.MIN
is changed,
AO2.P1
is set to
AO2.MIN
.
120
EB 6495-2 EN
Appendix
Default
setting
Setting