2
Start-up
2.1
Setting the system code number and control method
This ventilation controller allows ten different systems to be controlled. Each system is as-
signed a system code number. You can find a list of the different systems in section 4. In ad-
dition, the control method can be determined. The following control methods are available:
Control method
Display
Supply air control
Exhaust air control
Exhaust air cascade control
Room control
Room cascade control
The control methods and functions of the controller are described in sections 5, 6 and 7.
Every change in system code number or control method causes the assignment of sensors to
be reprogrammed: the sensor inputs required for the function blocks are activated and the
sensor inputs not used are deactivated. These settings can be changed manually.
You must set the system code number in the configuration level (see Fig. 30).
How to proceed:
Change to the configuration and parameter level.
PA
appears on the display.
Select
CO
level.
Press the enter key.
The currently active system code number, e.g. Anl 1, blinks on the display.
Press the enter key.
Anl
and
CO
blink quickly.
EB 5477 EN
17
Start-up