Parameter settings
Parameters
Range of values
Supply air temperature set point
0 to 50 °C
Exhaust air temperature set point
0 to 40 °C
Room temperature set point
0 to 40 °C
Supply air temperature minimum limit
0 to 50 °C
Supply air temperature maximum limit
0 to 50 °C
K
P
Heating coil
T
N
Heating coil
T
V
Heating coil
0.1 to 99.9
1 to 999 sec
- - - to 999 sec
Temperature set point of the slave loop
0 to 50 °C
K
P
Temperature master loop
0.1 to 99.9
Return air temperature minimum limit
0 to 100 °C
Return air temperature maximum limit
0 to 100 °C
Return air temperature maximum limit
Coordinate 1
Coordinate 2
0 to 100 °C
0 to 100 °C
Outdoor temperature
Coordinate 1
Coordinate 2
–50 to 20 °C
–50 to 20 °C
Return air temperature limit factor
0 to 10
Sustained room temperature
0 to 20 °C
Start-up when the outdoor temperature is smal-
ler
0 to 10 °C
Pump advance running time for start-up
0 to 900 sec
Control signal limit for Y1
0 to 100 %
Pump ON when the outdoor temperature is
smaller
–50 to 10 °C
Summer compensation when the outdoor tem-
perature is greater
–50 to 40 °C
Set point at an outdoor temperature of 32 °C
Supply air temperature
Exhaust air temperature
Room temperature
0 to 40 °C
0 to 40 °C
0 to 40 °C
Date when summer deactivation is enabled
01.01 to 31.12
114
EB 5477 EN