 12  

SH 8384-3 EN

Required conditions

Particle size and quantity

Oil content

Pressure dew point

Class 4

Class 3

Class 3

≤ 5 µm and 1000/m³

≤ 1 mg/m³

–20 °C or at least 10 K below the lowest ambi-

ent temperature to be expected

We recommend installing a supply pressure regulator/filter upstream of the positioner. 
For example, the SAMSON Type 4708 Supply Pressure Regulator with 5 µm filter car

-

tridge can be used.

 

Î

The supply air line has a minimum inside diameter of 4 mm.

Select the cross section and length of the line to ensure that the supply pressure at the po

-

sitioner on filling the actuator with air does not fall below the minimum limit.

 

Î

The positioner is mounted as prescribed.

 

Î

The vent opening at the back of the positioner remains open when the positioner is in-

stalled on site.

Electrical installation

 

Î

The positioner is connected to the electric power supply properly as described in the 
mounting and operating instructions.

 

Î

Only cables whose outside diameters are suitable for the cable glands are used.

 

Î

The electrical cables in Ex i circuits comply with the data that planning was based on.

 

Î

The cable glands and cover screws are fastened tightly to ensure that the degree of pro

-

tection is met.

 

Î

The installation requirements for the applicable explosion protection measures are ob

-

served.

 

Î

The special conditions specified in the explosion protection certificates are observed.

Operation

 

Î

When the optional inductive limit contact is used, Code 38 is set to YES.

 

Î

The inductive limit contact is adjusted mechanically to meet the specifications.

Tip

Содержание TROVIS 3730-3

Страница 1: ...Safety Manual SH 8384 3 EN Translation of original instructions Edition December 2016 Series 3730 Type 3730 3 Electropneumatic Positioner with HART communication...

Страница 2: ...y Property damage message or malfunction Additional information Recommended action DANGER WARNING NOTICE Note Tip The mounting and operating instructions for all supplied devices are included in the d...

Страница 3: ...ation The documents listed below contain descriptions of the start up functioning and operation of the positioner You can download these documents from the SAMSON website The documents marked with an...

Страница 4: ...4 SH 8384 3 EN Contents 1 Scope 5 2 Technical data excerpt from EB 8384 3 6 3 Safety related functions 8 4 Mounting connection and start up 10 5 Required conditions 11 6 Proof testing 13 7 Repairs 15...

Страница 5: ...in safety instrumented systems up to SIL 2 single device HFT 0 and SIL 3 redundant configuration HFT 1 The individual safety functions of the positioner are to be regarded as Type A elements in ac cor...

Страница 6: ...rotary actuators according to VDI VDE 3845 fixing levels 1 and 2 2 Technical data excerpt from EB 8384 3 Type 3730 3 Positioner also observe the technical data in the test certificates for explosion...

Страница 7: ...s is given Use is possible on observing the requirements of IEC 61511 and the required hard ware fault tolerance in safety instrumented systems up to SIL 2 single device HFT 0 and SIL 3 redundant conf...

Страница 8: ...ctive limit contact SJ2 SN NAMUR NC contact indicates the adjusted end posi tion in a safety instrumented system at terminals 41 42 See u EB 8384 3 for adjusting the limit contacts Fail safe action Fa...

Страница 9: ...valve 13 Analog position transmitter 2 Travel sensor 14 Software limit contact alarm 1 2 3 PD controller 15 Fault alarm output alarm 3 4 A D converter 16 Display 5 Microcontroller 17 Actuation of sole...

Страница 10: ...ing parts and accessories G 81 82 11 12 83 84 51 52 A2 A3 A1 41 42 31 32 A 31 32 24 V DC Solenoid valve optional mA control signal Not Ex Binary input of a PLC acc to IEC 61131 2 Pmax 400 mW or switch...

Страница 11: ...zed The positioner is suitable for the prevailing ambient temperature Versions Temperature range All 20 to 80 C With metal cable gland 45 to 80 C The limits in the test certificates additionally apply...

Страница 12: ...bed The vent opening at the back of the positioner remains open when the positioner is in stalled on site Electrical installation The positioner is connected to the electric power supply properly as d...

Страница 13: ...in a plant PFDavg Function testing Regularly check the safety function according to the test plan drawn up by the operator Record any faults in the positioner and inform SAMSON of them in writing Emer...

Страница 14: ...ner in Code 0 5 Set the voltage to 0 V DC terminals 81 82 6 Check whether the actuator is fully vented within the demanded time Connect a pressure gauge to check that the actuator has completely vente...

Страница 15: ...cal and physical processes Material fatigue Aging damage caused to organic materials e g plastics or elastomer by exposure to light and heat Chemical attack organic materials e g plastics or elastomer...

Страница 16: ...16 SH 8384 3 EN...

Страница 17: ...ces are classified as type A Die Konformit t des Entwicklungsprozesses der durchgef hrten FMEDA und der Aussa gen dieser Herstellererkl rung sind von der T V Rheinland Industrie Service durch das Zert...

Страница 18: ...iggered as fol lows The electrical input of the positioner is de energized o Types 3730 0 1 2 3 0 mA at terminals 11 12 o Types 3730 4 5 0 V voltage level at terminals IEC 1158 2 The electrical input...

Страница 19: ...4 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 samson samson de SAMSON AG SAMSON AG Guido K nig Zentralabteilungsleiter Produktmanagement und marketing Mess und Regeltechnik SAMSON...

Страница 20: ...SAMSON AG MESS UND REGELTECHNIK Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 samson samson de www samson de SH 8384 3 EN 2017 01 18 English...

Отзывы: