![Samson TROVIS 3730-1 Скачать руководство пользователя страница 58](http://html2.mh-extra.com/html/samson/trovis-3730-1/trovis-3730-1_mounting-and-operating-instructions_3935374058.webp)
58
EB 8384-1 EN
Code list
Error codes
E7
Actuator does not move
No supply air, mounting blocked.
No input signal or input signal below 3.7 mA
Recommended action
Check supply air, positioner mounting and mA input signal.
Re-initialize the positioner.
E8
Travel signal at lower/
upper limit
Wrong pin position, wrong lever, wrong attachment direction when
NAMUR attachment is used.
Recommended action
Check positioner mounting and re-initialize the positioner.
E9
Internal error
Switch off positioner and wait ten seconds before switching it on
again. If the error reappears, return positioner to SAMSON AG
for repair.
E10
to
E13
Device error
(internal)
Return positioner to SAMSON AG for repair.
E14
Data error
Reset positioner (P18). Reconfigure and re-initialize the positioner.
If the error reappears, return positioner to SAMSON AG for re-
pair.
E15
Device error
(internal)
Return positioner to SAMSON AG for repair.