20
EB 6116 EN
Technical data
9 Technical data
No explosion protection
Type 6116-0
With explosion
protection
Types 6116-1/-2/-3/-4/-5/-6/-7
Input
5)
4 to 20 mA, other signals on request
Minimum current >3.6 mA, load impedance ≤6 V (corresponding to 300 Ω at 20 mA)
Versions with explosion protection: load impedance 7 V (corresponding to 350 Ω at
20 mA)
Versions without switch-off electronics: R
i
= 200 Ω ± 7.5 %
Output
5)
0.2 to 1 bar (3 to 15 psi) (Type 6109 i/p Converter Module)
0.4 to 2 bar (6 to 30 psi) (Type 6112 i/p Converter Module)
Special ranges adjustable according to customer specifications:
Output range = Initial value
10)
+
Span ∆p with Type 6112 i/p Module
0.1 to 0.4 bar
+
0.75 to 1.0 bar
Module A
0.1 to 0.4 bar
+
1.0 to 1.35 bar
Module B
0.1 to 0.4 bar
+
1.35 to 1.81 bar
Module C
0.1 to 0.8 bar
+
1.81 to 2.44 bar
Module D
0.1 to 0.8 bar
+
2.44 to 3.28 bar
Module E
0.1 to 0.8 bar
+
3.28 to 4.42 bar
Module F
0.1 to 1.2 bar
+
4.42 to 5.94 bar
Module G
0.1 to 1.2 bar
+
5.94 to 8.0 bar
Module H
9)
Max. air output
capacity
3)
2.0 m³/h with an output of 0.6 bar (0.2 to 1.0 bar)
2.5 m³/h with an output of 1.2 bar (0.4 to 2.0 bar)
8.5 m³/h with an output of 5.0 bar (0.1 to 8.0 bar)
Supply air
At least 0.4 bar above the upper signal pressure range value, max. 10 bar without sup-
ply pressure regulator, max. 6 bar for Ex d version
Air quality acc. to
ISO 8573-1: 2001
Max. particle size and density: Class 4 · Oil content: Class 3 · Pressure dew point: Class
3 or at least 10 K below the lowest ambient temperature to be expected
Air consumption
2)
0.08 m
n
³/h at 1.4 bar
0.1 m
n
³/h at 2.4 bar
Max. 0.26 m
n
³/h at 10 bar
Characteristic
Characteristic: Output linear to input
Hysteresis
≤0.3 % of upper range value
Deviation from
terminal-based
conformity
≤1 % of upper range value (for upper range values up to 5 bar);
more exact values on request
≤1.5 % of upper range value (for upper range values above 5 bar)
Effect in % of the
upper range value
Supply air: 0.1 %/0.1 bar
2)
Alternating load, supply air failure, interruption of the input current: < 0.3 %
Ambient temperature: lower range value < 0.03 %/K, span < 0.03 %/K
Содержание 6000 Series
Страница 27: ...EB 6116 EN 27...
Страница 28: ...28 EB 6116 EN...
Страница 29: ...EB 6116 EN 29...
Страница 30: ...30 EB 6116 EN...
Страница 31: ...EB 6116 EN 31...
Страница 32: ...32 EB 6116 EN...
Страница 33: ...EB 6116 EN 33...
Страница 34: ...34 EB 6116 EN...
Страница 35: ...EB 6116 EN 35...
Страница 36: ...36 EB 6116 EN...
Страница 37: ...EB 6116 EN 37...
Страница 38: ...38 EB 6116 EN...
Страница 39: ...EB 6116 EN 39...