Availability checkback
CHECK_BACK_OPT
States:
Default:
Defined the availability of the status bits in CHECK_BACK.
0 = Not available
1 = Available
1
Availability diagnosis
DIAGNOSIS_OPT
States:
Default:
Defined the availability of the status bits in DIAGNOSIS.
0 = Not available
1 = Available
1
Binary input
IDENT_BINARY_INPUT (M)
States:
Default:
Describes whether and how the binary switch option is evaluated.
0 = Not evaluated
1 = Actively open
2 = Actively closed
0
Calibration
alarm message
SELF_CALIB_WARNING (M)
States:
Default:
Additional alarm messages of the initiated calibration procedure.
0 = Undetermined
13 = Wrong selection of rated travel or transmission
15 = Air leakage in pneumatic system (during initialization)
254 = Successful
255 = No valid data at the application
0
Calibration command
SELF_CALIB_CMD
States:
Command to start manufacturer-specific calibration procedures in the field device.
0 = No test, standard control operation
1 = Zero calibration
2 = Initialization
7 = Reset total valve travel
10 = Reset "Control loop fault"
255 = Abort process in action
Calibration status
SLF_CALIB_STATUS
States:
Manufacturer-specific status of the calibration procedure started with SELF_CALIB_CMD.
0 = Undetermined
2 = Aborted
4 = Error in mechanics /pneumatics
11 = Timeout
17 = Initialization status: determination of mechanical stops
19 = Initialization status: determination of minimum transit times
20 = Initialization aborted due to activated forced venting function
30 = Zero error
254 = Successful
EB 8382-2 EN
55
List of parameters