Code list

Code 

no.

Parameter

 – Readings/

values [default setting]

Description

36* Reset

[No], Std, diAG, ESC

Std:

Resets all parameters and diagnosis data to their default set-

tings. After a reset, the positioner must be re-initialized.

diAG: Resets diagnosis data only. Plotted reference graphs and logs 

remain saved.

The positioner does not need to be re-initialized.

37* Position transmitter

No, YES

Read only
Indicates whether an optional position transmitter is installed.

38* Inductive alarm

[No], YES, ESC

Indicates whether the inductive limit switch option is installed or not.

39 Set point deviation e info

–99.9 to 99.9 %

Read only

Indicates the deviation from the target position (e = w – x).

40 Transit time Open info

[0] to 240 s

Read only

Minimum opening time determined during initialization.

41 Transit time Closed info

[0] to 240 s

Read only

Minimum closing time determined during initialization.

42 Auto-w info

0.0 to 100.0 % of the 

span

Read only
Indicates the applied automatic set point with corresponding 4 to 

20 mA signal.

43 Firmware info

Read only

Indicates the positioner type and current firmware version in alter

-

nating sequence.

44 y info

[0] to 100 %, 0P, MAX, 

– – –

Read only

Indicates the control signal y in % in relation to the travel range de

-

termined during initialization.
MAX:

The positioner builds up its maximum output pressure, see 

description in Code 14 and 15.

0P:

The positioner vents completely, see description in Code 14 

and 15.

– – –:

The positioner is not initialized.

Содержание 3730-2

Страница 1: ...Mounting and Operating Instructions EB 8384 2 EN 1300 1611 Firmware version 1 56 Edition April 2016 Series 3730 Type 3730 2 Electropneumatic Positioner EB CD...

Страница 2: ...epartment aftersalesservice samson de The mounting and operating instructions for the devices are included in the scope of delivery The latest documentation is available on our website www samson de P...

Страница 3: ...double acting actuators 38 4 6 1 Reversing amplifier 1079 1118 or 1079 1119 40 4 7 Attachment of external position sensor 42 4 7 1 Mounting the position sensor with direct attachment 43 4 7 2 Mountin...

Страница 4: ...sed on a manually selected range 70 7 6 4 SUb Substitute calibration 71 7 7 Zero calibration 74 7 8 Reset to default settings 75 8 Operation 76 8 1 Enabling and selecting parameters 76 8 2 Operating m...

Страница 5: ...alve characteristic selection 107 Index 126 The functions of the EXPERTplus Valve Diagnostics are described in the Operating Instructions u EB 8389 EB 8389 is included on the enclosed CD ROM and is av...

Страница 6: ...us diagnostics functions Code 48 added Positioner in EXPERTplus version with extended diagnostics features An initialization procedure in progress can be canceled by pressing the rotary pushbutton The...

Страница 7: ...input with following actions Transmit switching state Activate local write protection Switch between automatic and manual modes Various diagnostic functions u EB 8389 EXPERTplus valve diagnostics The...

Страница 8: ...rized to work on explosion pro tected devices in hazardous areas Any hazards that could be caused in the valve by the process medium the signal pres sure or by moving parts are to be prevented by taki...

Страница 9: ...e limit switch Without 0 SJ2 SN NC contact 1 0 SJ2 S1N NO contact 0 32 Solenoid valve Without 0 With 24 V DC 4 Analog position transmitter Without 0 With 1 External position sensor Without 0 With 0 1...

Страница 10: ...m and two configurable software limit switches are used to indicate the end positions of the valve The valve position is transmitted as a either an angle of rotation or travel to the pick up lever and...

Страница 11: ...sories Direct attachment to SAMSON Type 3277 Actuators Attachment to actuators according to IEC 60534 6 NAMUR Attachment according to VDI VDE 3847 Attachment to Type 3510 Micro flow Valve Attachment t...

Страница 12: ...ice versa This function is not performed if the posi tioner is in the fail safe position mode SAFE Various diagnostic functions u EB 8389 EXPERTplus valve diagnostics The optional binary input can onl...

Страница 13: ...o ISO 8573 1 Max particle size and density Class 4 Oil content Class 3 Pressure dew point Class 3 or at least 10 K below the lowest ambient temperature to be expected Signal pressure output 0 bar up t...

Страница 14: ...nstrumented systems is given Use is possible on observing the requirements of IEC 61511 and the required hardware fault tolerance in safety instrumented systems up to SIL 2 single device HFT 0 and SIL...

Страница 15: ...orresponding to 4 8 mA at 24 V 114 mW Signal 0 no response 12 V emergency shutdown at 0 V Signal 1 response 19 V Service life 5 x 106 switching cycles KV coefficient 0 15 Analog position transmitter T...

Страница 16: ...ion in hazardous areas Temperature range 40 to 130 C Tightening torque 20 5 Nm Binary input Galvanically isolated Switching behavior configured by software e g TROVIS VIEW DTM Active switching behavio...

Страница 17: ...3 08 19 Number RU C DE 08 B 00697 1Ex ia IIC T6 T5 T4 Gb X Ex tb III T 80 C Db X Date 2014 12 15 Valid until 2019 12 14 CCoE Number A P HQ MH 104 1339 Ex ia IIC T6 Date 2012 01 27 Valid until 2017 01...

Страница 18: ...IIIC T80 C Db Date 2013 08 19 27 JIS Number TC18159 Ex ia IIC T6 Valid until 2016 11 25 28 2 Number PTB 03 ATEX 2016 X II 3G Ex nA II T6 II 3G Ex ic IIC T6 II 3D Ex tc IIIC T80 C IP66 Date 2013 08 16...

Страница 19: ...EB 8384 2 EN 19 Design and principle of operation...

Страница 20: ...gnment of lever and pin position Attach the positioner to the control valve only using the mounting parts and accessories as specified in Table 1 to Table 6 Observe the type of attachment Observe the...

Страница 21: ...to 50 0 M 50 Attachment according to IEC 60534 6 NAMUR SAMSON valves with Type 3271 Actuator Adjustment range at positioner 1 Other control valves Required lever Assigned pin position Actuator size Ra...

Страница 22: ...ight so that the mounting screw is located in the groove of the actuator stem 4 Mount cover plate 10 with narrow side of the cut out Fig 3 on the left pointing towards the signal pressure connection M...

Страница 23: ...r right attachment Cut out of cover plate NOTICE Only use the connecting plate 6 included in the accessories to connect supply and output Never screw threaded parts directly into housing 1 Lever 1 1 N...

Страница 24: ...4 Insert formed seal 15 into the groove of the positioner housing 5 Place positioner on the cover plate in such a manner that the follower pin 2 rests on the top of the follower clamp 3 Adjust the le...

Страница 25: ...ver plate 10 Actuator stem extends Actuator stem retracts Connection block old with switch plate 13 Actuator stem 1 Lever 1 1 Nut 1 2 Disk spring 2 Follower pin 3 Follower clamp 10 Cover plate 11 Cove...

Страница 26: ...to the em bossed scale so that the follower plate 3 is shifted by half the angle range to the NAMUR bracket the slot of the follower plate is centrally aligned with the NAMUR bracket at mid valve trav...

Страница 27: ...60 mm XL and L lever Fig 5 Attachment according to IEC 60534 6 NAMUR 1 Lever 1 1 Nut 1 2 Disk spring 2 Follower pin 3 Follower plate 3 1 Follower plate 6 Connecting plate 6 1 Seals 7 Pressure gauge br...

Страница 28: ...itioner attachment The Y2 port can be used for air purging of the spring chamber 1 Place follower clamp 3 on the actuator stem align it and screw tight so that the mounting screw is located in the gro...

Страница 29: ...1 2 Disk spring 2 Follower pin 3 Follower clamp 4 Blanking plug 5 Sealing plug 6 Adapter bracket 6 1 Screws 6 2 Formed seal 6 3 Screws 11 Cover 11 1 Vent plug 12 Connecting plate 12 1 Gasket 13 Adapt...

Страница 30: ...ent plug 11 1 into the Exh connection 11 For fail safe action actuator stem ex tends seal the Y1 port with a blanking plug For fail safe action actuator stem re tracts connect the Y1 port to the signa...

Страница 31: ...the formed plate 15 which is placed around the yoke screw the four studs into the NAMUR connection block 10 Place the NAMUR connection block on the rod and position the formed plate 15 on the opposite...

Страница 32: ...connection block using the screws 13 1 9 Insert the vent plug into the Exh connec tion 10 Place the positioner on the adapter block 13 in such a manner that the follower pin 2 rests on the top of the...

Страница 33: ...3 Follower plate 3 1 Follower plate 4 Blanking plug 5 Sealing plug 6 Adapter bracket 6 1 Screws 6 2 Formed seal 6 3 Screws 10 NAMUR con nection block 11 Screw with toothed lock washer 13 Adapter bloc...

Страница 34: ...sure the two seals are seated properly 7 Unscrew the standard M lever 1 includ ing follower pin 2 from the positioner shaft 8 Take the S lever 1 and screw the follow er pin 2 in the hole for pin posit...

Страница 35: ...ut 1 2 Disk spring 2 Follower pin 3 Follower plate 6 Connecting plate 6 1 Seals 7 Pressure gauge bracket 8 Pressure gauge mounting kit 9 Stem connector 9 1 Bracket 9 2 Bolt 9 3 Screws 10 Bracket 10 1...

Страница 36: ...sitioner s M lever 1 Use the metal follower pin 5 mm included in the mounting kit and screw tight into the hole for pin position 90 7 Place positioner on the top bracket 10 and fasten tight Taking the...

Страница 37: ...nto housing Legend for Fig 10 and Fig 11 1 Lever 1 1 Nut 1 2 Disk spring 2 Follower pin 3 Follower clamp Fig 10 4 Coupling wheel 4 1 Screw 4 2 Disk spring 4 3 Scale plate 5 Actuator shaft Adapter for...

Страница 38: ...pressure gauge bracket 7 with pressure gauges on the positioner making sure the two seals 6 1 are seated properly Dou ble acting springless rotary actuators re quire the use of a reversing amplifier...

Страница 39: ...4 3 Adhesive label 5 Actuator shaft or adapter 5 1 Adapter 6 Connecting plate only for G 6 1 Seals 7 Pressure gauge bracket 8 Pressure gauge mounting kit 10 Adapter housing 10 1 Screws 11 Spacer SAMSO...

Страница 40: ...accessories in Table 5 to the positioner Make sure that both O rings 6 1 are seated correctly 2 Thread the special nuts 1 3 from the ac cessories of the reversing amplifier into the boreholes of the...

Страница 41: ...1 A2 Z A1 Output 38 Supply 9 Output 38 Supply 9 1 3 1 2 1 1 From the positioner Control signals to the actuator 1 Reversing amplifier 1 1 Special screws 1 2 Gasket 1 3 Special nuts 1 4 Rubber seal 1 5...

Страница 42: ...cting plate 6 or a pressure gauge bracket 7 must be fixed to the housing depending on the accessory chosen Make sure the seals 6 1 are correctly inserted see Fig 5 bot tom right For the electrical con...

Страница 43: ...rect symbol for the fail safe action actuator stem extends or actuator stem retracts is aligned with the marking Fig 15 below Make absolutely sure that the gasket for the connecting plate 9 is correct...

Страница 44: ...the follower pin 2 is to be used from the travel table on page 21 The positioner is delivered with the M lever in pin position 35 on the sensor If necessary remove the follower pin 2 from its pin posi...

Страница 45: ...vels se lect the lever and pin position from the travel table on page 21 L and XL levers are in cluded in the mounting kit 3 Place the lever 1 and disk spring 1 2 on the sensor shaft Place the lever i...

Страница 46: ...acket 21 3 Select the S lever 1 from the accessories and screw the follower pin 2 into the hole for pin position 17 Place the lever 1 and disk spring 1 2 on the sensor shaft Place the lever in mid pos...

Страница 47: ...te 21 3 Replace the follower pin 2 normally at tached to the lever 1 with the metal fol lower pin 5 mm from the accessories and screw it into the hole for pin position 90 4 Place the lever 1 and disk...

Страница 48: ...unction due to incorrect fastening Fasten the leakage sensor using a torque of 20 5 Nm The M8 threaded connection on the NAMUR rib should preferably be used to mount the sensor Fig 19 If the positione...

Страница 49: ...NAMUR rib or attachment to rod type yokes All mounting kits from Table 3 can be used Connecting plate in stainless steel Attachment to rotary actuators All mounting kits from Table 5 can be used exce...

Страница 50: ...ssure and damage the positioner when the exhausting components respond suddenly Note 4 11 Required mounting parts and accessories Table 1 Direct attachment to Type 3277 5 Actuator Fig 3 Order no Mount...

Страница 51: ...8 240 cm Steel G G 3 8 1400 6444 NPT 3 8 NPT 1402 0911 Stainless steel G G 3 8 1400 6445 NPT 3 8 NPT 1402 0912 350 cm Steel G G 3 8 1400 6446 NPT 3 8 NPT 1402 0913 Stainless steel G G 3 8 1400 6447 NP...

Страница 52: ...ting plate 6 G 1400 7461 NPT 1400 7462 Pressure gauge bracket 7 G 1400 7458 NPT 1400 7459 Pressure gauge mounting kit up to max 6 bar output supply Stainless steel brass 1400 6950 Stainless steel stai...

Страница 53: ...with 320 cm and to VETEC Type S320 heavy duty version 1400 5891 and 1400 9526 Attachment to Camflex II 1400 9120 Accessories Connecting plate 6 G 1400 7461 NPT 1400 7462 Pressure gauge bracket 7 G 140...

Страница 54: ...or with 60 cm See Fig 17 1400 7469 Attachment to rotary actuators VDI VDE 3845 September 2010 see section 15 1 for details Actuator surface corresponds to fixing level 1 Size AA1 to AA4 with follower...

Страница 55: ...f malfunction due to failure to comply with required air quality Only use supply air that is dry and free of oil and dust Read the maintenance instructions for up stream pressure reducing stations Blo...

Страница 56: ...of electric shock and or the formation of an explosive atmosphere For electrical installation observe the rele vant electrotechnical regulations and the ac cident prevention regulations that apply in...

Страница 57: ...of conformity and its ad denda apply when interconnecting the equipment with energy limited circuits in type of protection Ex nL IIC Cable entry Cable entry with M20 x 1 5 cable gland 6 to 12 mm clam...

Страница 58: ...teel 1400 7114 In positioners for attachment according to VDI VDE 3847 the terminal designation of the limit switches 41 42 and 51 52 as well as the OPEN and CLOSED wording can be changed by turning t...

Страница 59: ...the limit values of the output circuits conforming to EN 60947 5 6 Observe the relevant regulations for installa tion in hazardous areas For applications in safe areas non hazard ous areas limit swit...

Страница 60: ...ion Q The volume restriction serves to adapt the air output capacity to the size of the actuator Depending on the air passage at the actua tor two fixed settings are available For actuators smaller th...

Страница 61: ...esignation Position Parameters Limit switch alarm 1 AUtO Automatic CL Clockwise CCL Counterclockwise Err Error ESC Stop HI ix higher than 21 6 mA LO ix lower than 2 4 mA LOW w too low MAN Manual setti...

Страница 62: ...n in degrees in relation to the mid axis One bar element corre sponds to approximately a 5 angle of rota tion The fifth bar element blinks reading 30 if the permissible angle of rotation has been exce...

Страница 63: ...or retracting Do not touch or block the actuator stem The positioner performs a test in the start up phase while following its automation task at the same time During the start up phase operation on...

Страница 64: ...he actuator in SAMSON actuators The SIDE position applies for actuators with a signal pressure connection at the side e g Type 3271 5 The BACK position applies for actuators with a signal pressure con...

Страница 65: ...be comes invalid Enable configuration Default No Turn g Code 3 display No Press Code 3 blinks Turn YES Press display Limit the signal pressure Pressure limit Default No Turn Code 16 Press Code 16 bli...

Страница 66: ...4 Risk of injury due to the actuator stem ex tending or retracting Before exchanging the lever or changing the pin position disconnect the supply air and electrical auxiliary power 7 6 Initialization...

Страница 67: ...ization Initialization successfully completed Positioner in automatic mode The time required for the initialization proce dure depends on the actuator transit time and can take a few minutes After a s...

Страница 68: ...7 6 1 MAX Initialization based on maximum range The positioner determines travel angle of ro tation of the closing member from the CLOSED position to the opposite travel stop and adopts this travel an...

Страница 69: ...with out collision If this is the case the indicated nominal range is adopted with the limits of travel angle range start Code 8 and trav el angle range end Code 9 as the operat ing range The maximum...

Страница 70: ...n Turn the rotary pushbutton clockwise in small steps The valve must be moved with a monotonically increasing signal pressure The positioner calculates the differential trav el angle from the OPEN and...

Страница 71: ...a result a high level of accuracy cannot be expected A different initialization mode should be selected if the plant allows it The substitute calibration is used to replace a positioner while the proc...

Страница 72: ...position on lever see relevant section on attachment Press Turn Code 5 Press Code 5 blinks Turn Nominal travel of the valve Press Select the initialization mode Init mode Default MAX Turn Code 6 Press...

Страница 73: ...ion direction of rotation causing the valve to move to the CLOSED position view onto positioner display Default CCL counterclockwise mm Blocking position Default 0 Turn Code 34 Press Code 34 blinks Tu...

Страница 74: ...te in automatic mode the parameters KP and TV must be slightly corrected Proceed as fol lows Set TV Code 18 to 4 If the positioner still oscillates the gain KP Code 17 must be decreased until the po s...

Страница 75: ...and setting parameters as well as the diagnosis to the factory default settings see code list in sec tion 14 Enable configuration Turn g Code 3 display No Press Code 3 blinks Turn YES Press display Re...

Страница 76: ...g in Code 3 Turn YES Press display Configuration is enabled You can now configure codes one after the other Turn to select the required code Press to activate the selected code The code number starts...

Страница 77: ...position The positioner automatically returns to Code 0 if no settings are made within 120 seconds but remains in the manual mode Switch to automatic mode Turn Code 0 Press Code 0 blinks Turn AUtO Pr...

Страница 78: ...uc cessfully completed Maintenance required The positioner still performs its control task with restrictions A maintenance demand or above average wear has been determined The wear tolerance will soon...

Страница 79: ...put to be switched The Function check condensed state can also activate the fault alarm output Code 32 The Maintenance required Maintenance demanded condensed state can also ac tivate the fault alarm...

Страница 80: ...ted in such a way that it will provide a signal in both end positions of the valve The switch how ever can also be adjusted to indicate inter mediate valve positions The required switching function i...

Страница 81: ...ponds You can measure the switching voltage as an indicator Contact function Tag leaving the field contact is closed Tag entering the field contact is opened For OPEN position 1 Initialize the positio...

Страница 82: ...e cable connector 11 5 Guide the cable in such a manner that the plastic cover can be placed back onto the positioner Insert the fixing screws 2 and screw tight Attach the clamping plate 8 onto the pr...

Страница 83: ...e already been operated outside hazardous areas and are intended for future use inside hazardous areas must comply with the safety requirements placed on serviced devices Before being operated inside...

Страница 84: ...done using labels 13 Maintenance calibration and work on equipment Interconnection with intrinsically safe cir cuits to check or calibrate the equipment in side or outside hazardous areas is to be per...

Страница 85: ...he positioner is initialized If the positioner is not initialized the position of the lever in relation to the longitudinal axis is indicated in degrees Note can only be selected when Code 0 MAN 2 Rea...

Страница 86: ...sing increasing Increasing decreasing ESC Direction of action of the set point w in relation to the travel angle x Automatic adaptation AIR TO OPEN On completing initialization the direction of action...

Страница 87: ...C Limits travel angle to the entered value upper limit The characteris tic is not adapted Example In some applications it is better to limit the valve travel e g if a certain minimum medium flow is re...

Страница 88: ...or completely vented with AIR TO CLOSE This action always lead to the valve being completely opened Codes 14 15 have priority over Codes 8 9 10 11 Codes 21 22 have priority over Codes 14 15 Example Se...

Страница 89: ...plug valve equal percentage 7 Segmented ball valve linear 8 Segmented ball valve equal percentage 9 User defined defined over operator software Note The various characteristics are listed in the Appe...

Страница 90: ...re limit switch alarms A1 and A2 when activated when the positioner is initialized 1 Explosion protected version according to EN 60947 5 6 0 A1 2 2 mA A2 1 0 mA 1 A1 1 0 mA A2 1 0 mA 2 A1 2 2 mA A2 2...

Страница 91: ...UN software limit switch A1 to 2 2 mA RUN 2 2 RUN software limit switch A2 to 2 2 mA RUN 3 3 RUN fault alarm contact A3 to 1 0 mA 29 Position transmitter x ix 3 ESC Operating direction of the position...

Страница 92: ...ion check condensed state No Function check condensed state does not cause an error message to be issued Note Regardless of the condensed state the fault alarm output always switches when the error co...

Страница 93: ...ndicates the deviation from the target position e w x 40 Transit time Open info 0 to 240 s Read only Minimum opening time determined during initialization 41 Transit time Closed info 0 to 240 s Read o...

Страница 94: ...ification blinking Maintenance alarm If No message is assigned to the error code as the status classification the error is not included in the condensed state A status classification is assigned to ev...

Страница 95: ...ards permissible Mechanical or pneumatic fault e g wrong lever selected or supply pressure too low to move to the required position Status classification Maintenance required Recommended action Check...

Страница 96: ...ositioner tuning is impossible Status classification Maintenance required Recommended action Check the volume restriction setting as described in section 7 2 Re initialize the positioner 56 Pin positi...

Страница 97: ...zero calibra tion over Code 6 see section 7 7 We recommend to re initialize the positioner if zero deviates by more than 5 59 Auto correction Errors in the positioner s data section are detected detec...

Страница 98: ...es to emergency mode where the position cannot be accurately controlled anymore However the positioner continues operation according to its set point so that the process remains in a safe state Status...

Страница 99: ...data can be written to the memory e g because written data deviate from read data The valve moves to the fail safe position Status classification Maintenance alarm cannot be classified Recommended act...

Страница 100: ...with cold start values Status classification Maintenance required Recommended action Return positioner to SAMSON AG for repair 71 General parameters Error in parameters not critical to control operat...

Страница 101: ...Status classification No message Recommended action Merely information confirm if necessary No further action required 77 Software loading error When the positioner starts operation for the first tim...

Страница 102: ...ation Status classification Maintenance required cannot be classified Recommended action Confirm error Check and if necessary perform a new reference test 81 Reference graphs Error occurred during plo...

Страница 103: ...34 210 28 14 80 164 Output 38 Supply 9 86 70 15 46 34 70 70 28 Schild 58 58 Pressure gauge bracket or connecting plate Attachment according to IEC 60534 6 Lever see Fig 29 External position sensor Dir...

Страница 104: ...EN Dimensions in mm Attachment according to VDI VDE 3847 to Type 3277 Attachment according to VDI VDE 3847 to a NAMUR rib 62 164 3 8 200 164 164 13 62 24 Lever see Fig 29 Fig 27 Attachment according t...

Страница 105: ...put A2 Supply 9 50 80 58 130 49 59 79 76 50 150 Reversing amplifier optional Connecting plate G or NPT Reversing amplifier Type 3710 see drawing of heavy duty version for dimensions 1079 1118 1079 111...

Страница 106: ...o VDI VDE 3845 September 2010 A M6 C B 25 Mmin d D Fixing level 2 bracket surface Fixing level 1 actuator surface Actuator Dimensions in mm Size A B C d Mmin D AA0 50 25 15 5 5 for M5 66 50 AA1 80 30...

Страница 107: ...ge select characteristic 2 0 50 100 0 50 100 Travel angle of rotation Reference variable 0 50 100 0 50 100 Travel angle of rotation Reference variable 16 Valve characteristic selection The characteris...

Страница 108: ...lve linear select characteristic 5 VETEC rotary plug valve equal percentage select characteristic 6 0 50 100 0 50 100 Travel angle of rotation Reference variable 0 50 100 0 50 100 Travel angle of rota...

Страница 109: ...EB 8384 2 EN 109...

Страница 110: ...110 EB 8384 2 EN...

Страница 111: ...EB 8384 2 EN 111...

Страница 112: ...112 EB 8384 2 EN...

Страница 113: ...EB 8384 2 EN 113...

Страница 114: ...114 EB 8384 2 EN...

Страница 115: ...EB 8384 2 EN 115...

Страница 116: ...116 EB 8384 2 EN...

Страница 117: ...EB 8384 2 EN 117...

Страница 118: ...118 EB 8384 2 EN...

Страница 119: ...EB 8384 2 EN 119...

Страница 120: ...120 EB 8384 2 EN...

Страница 121: ...EB 8384 2 EN 121...

Страница 122: ...122 EB 8384 2 EN...

Страница 123: ...EB 8384 2 EN 123...

Страница 124: ...124 EB 8384 2 EN...

Страница 125: ...EB 8384 2 EN 125...

Страница 126: ...ry contact Electrical connection 56 Binary input 12 Blocking position canceling 74 C Code list 85 102 Condensed state 78 Configuration At the positioner 76 Connections Electric 56 Pneumatic 55 Control...

Страница 127: ...tic connections 55 Principle of operation 10 R Reading Display 60 On display 61 Turn by 180 64 Reset 75 Reversing amplifier 38 Rotary pushbutton 60 S Select characteristic 89 107 108 Serial interface...

Страница 128: ...SAMSON AG MESS UND REGELTECHNIK Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 samson samson de www samson de EB 8384 2 EN 2016 09 30 English...

Отзывы: