![Samson 3321 Скачать руководство пользователя страница 31](http://html2.mh-extra.com/html/samson/3321/3321_mounting-and-operating-instructions_3790213031.webp)
EB 8111/8112 EN
31
Mounting and start-up
Noise emission
Trims with flow dividers can be used to re
-
duce noise emission (see
u
T 8081).
5.2.3 Installing the control
valve
1. Close the shut-off valve in the pipeline
while the valve is being installed.
2. Remove the protective caps from the
valve ports before installing the valve.
3. Lift the valve using suitable lifting equip
-
ment to the site of installation (see sec
-
tion 4.2.2). Observe the flow direction
through the valve. The arrow on the
valve indicates the direction of flow.
4. Make sure that the correct flange gaskets
are used.
5. Bolt the pipe to the valve free of stress.
6. Depending on the field of application,
allow the valve to cool down or heat up
to reach ambient temperature before
start up.
7. Slowly open the shut-off valve in the
pipeline after the valve has been in
-
stalled.
Risk of valve damage due to a sudden pres
-
sure increase and resulting high flow veloci
-
ties.
Slowly open the shut-off valve in the pipeline
during start-up.
8. Check the valve to ensure it functions
properly.
5.3 Quick check
SAMSON valves are delivered ready for
use. To test the valve's ability to function, the
following quick checks can be performed:
Tight shut-off
1. Close the valve.
2. Slowly open the shut-off valve in the
pipeline.
Risk of valve damage due to a sudden
pressure increase and resulting high flow
velocities.
Slowly open the shut-off valve in the pipeline
during start-up.
3. Check the valve for leakage (visual in
-
spection).
Travel motion
The movement of the actuator stem must be
linear and smooth.
Î
Open and close the valve, observing the
movement of the actuator stem.
Î
Apply the maximum and minimum con
-
trol signals to check the end positions of
the valve.
Î
Check the travel reading at the travel in
-
dicator scale.
Fail-safe position
Î
Shut off the signal pressure line.
Î
Check whether the valve moves to the
fail-safe position.
NOTICE
!
NOTICE
!
Содержание 3321
Страница 11: ...EB 8111 8112 EN 11 Safety instructions and measures...
Страница 27: ...EB 8111 8112 EN 27 Measures...
Страница 33: ...EB 8111 8112 EN 33 Mounting and start up...
Страница 35: ...EB 8111 8112 EN 35 Operation...
Страница 45: ...EB 8111 8112 EN 45 Servicing...
Страница 53: ...EB 8111 8112 EN 53...
Страница 55: ...EB 8111 8112 EN 55 15 11 12 16 2 5 1 4 13 17 14 63 62 5 2 8 Type 3321 DN 65 to 100 NPS 2 to 4...