46
EB 2512 EN
Malfunctions
Table 10:
Troubleshooting
Malfunction
Possible reasons
Recommended action
Downstream pressure
drops below the
adjusted set point.
Regulator installed against the flow.
Î
Install the regulator so that the direction of flow
matches the direction indicated by the arrow on
the body.
Regulator or K
VS
/C
V
coefficient too
small
Î
Check the sizing.
Î
Change K
VS
/C
V
coefficient, if necessary or
install a different sized regulator.
Î
Contact SAMSON's After-sales Service
department.
Pressure tapped at the wrong place
(regulator with external control line).
Î
Reconnect the control line at another point.
Î
Do not connect the control line at pipe bends or
necks.
Foreign particles blocking the plug
Î
Remove foreign particles.
Î
Replace damaged parts.
Î
Contact SAMSON's After-sales Service
department.
Compensation chamber in the wrong
position or too small (with steam).
Î
Reconnect compensation chamber at a different
place or replace it (see section 7.7).
Control line blocked
Î
Clean the control line and screw fittings.
Strainer blocked.
Î
Clean strainer.
Jerky control
response
Increased friction, e.g. due to foreign
particles between seat and plug.
Î
Remove foreign particles.
Î
Replace damaged parts.
Î
Contact SAMSON's After-sales Service
department.
Loud noises
High flow velocity, cavitation.
Î
Check the sizing.
Î
Install larger regulator, if necessary.
Î
Install flow divider with gases and steam.
Leakage at the
actuator.
Defective operating diaphragm/bel-
lows.
Î
Replace damaged diaphragm/bellows.
Leakage at the bellows
seal.
Defective bellows seal
Î
Replace bellows seal.
Î
Contact SAMSON's After-sales Service
department.
Red mark appears at
the diaphragm rupture
indicator (actuator
with two diaphragms).
Defective operating diaphragm
Î
Replace damaged operating diaphragm.