AC input side wiring and breaker sizes depend upon the maximum continuous AC input cur-
rent under various operating conditions described in the succeeding paragraphs.
The Maximum Load Current on the output side has to be limited to the rated output Amp
capacity of the specific model when operating in Inverter Mode (Column 1 ).
When Grid / Generator input is available and the unit is operating in Charging / Pass
Through Mode, the AC Input Current will be determined as follows:
-
The maximum possible AC Input Current (Column 4) for a particular model will be
equal to the sum of the rated AC Side battery Charging Current (Column 3) and the
rated Pass Through current (Column 2). rated Pass Through Current (Column 2) = the
rated Output Current in Inverter Mode (Column 1).
-
The AC Input current in Charging / Pass Through Mode will be restricted by the maximum
Amp rating of the Generator or the Amp rating of the breaker in the Grid branch Circuit
that is feeding the unit. The AC Input Current drawn by the unit can be programmed to
the desired limit (Column 5) to match the output Amp rating of the Generator or the Amp
rating of breaker in the Grid branch Circuit. Optional remote Control EVO-rC is required to
change this limit (See page 26 of Appendix A under Section 4.5, Group 2 Parameter Setup
for Input Settings -"GrID MAX CUrrENT" and "GEN MAX CUrrENT").
-
All the 4 models EVO-2212E, 2224E, 3012E and 4024E come with Input "GrID MAX
CUrrENT" and "GEN MAX CUrrENT"" set at safe default value of 16A. This default
value has been used for convenience of powering the units from the standard 16A
mains power inlet plug on 230 VAC, 50Hz motorhome / caravan / vehicle.
tAbLe 3.2.1 SiZing oF griD AnD generAtor inPut wiring
AnD breAkerS For eVo-2212e AnD eVo-2224e
Model no. and
rated output
Power in inverter
Mode
(Column 1)
rated AC
Pass through
Current
(See note 1)
(Column 2)
rated AC
Charging
Current
(See note 2)
(Column 3)
total rated AC
input Current
(Columns 2 +3)
(See note 3)
(Column 4)
Programmed
Value of
"griD MAX
Current" and
"gen MAX
Current"
(See note 4)
(Column 5)
external
breaker Size
based on
Column 5
(See note 5)
(Column 6)
Conductor
Size based on
breaker Size
at Column 6
(See note 6)
(Column 7)
EVO-2212E
(2200VA, 10A)
10A
9A
19A
19A
20A
2.5 mm
2
or
AWG #14
EVO-2224E
(2200VA, 10A)
10A
10A
20A
20A
20A
tAbLe 3.2.2 SiZing oF griD AnD generAtor inPut wiring AnD breAkerS For eVo-3012e
Model no. and
rated output
Power in inverter
Mode
(Column 1)
rated AC
Pass through
Current
(See note 1)
(Column 2)
rated AC
Charging
Current
(See note 2)
(Column 3)
total rated AC
input Current
(Columns 2 +3)
(See note 3)
(Column 4)
Programmed
Value of
"griD MAX
Current" and
"gen MAX
Current"
(See note 4)
(Column 5)
external
breaker Size
based on
Column 5
(See note 5)
(Column 6)
Conductor
Size based on
breaker Size
at Column 6
(See note 6)
(Column 7)
EVO-3012E
(3000VA, 13A)
13A
12A
25A
25A
25A
4 mm
2
or
AWG #12