Parameter Setup
4.2.2 CHAnGinG / enteRinG PARAMeteR VALUeS
Each parameter has a programmable range of values specific to the model number of the
EVO
TM
. Please refer to Tables 4.4 to 4.8 for details.
During parameter programming
, the
displayed numerical value of the parameter consists of multiple digits that are necessary
to display the highest numerical value within the programmable range. For example, the
programmable range for the parameter BULK CURRENT for EVO-3012 is 0-130A (Table 4.4).
The highest numerical value is “130” and consists of 3 digits. Hence, for EVO-3012, the
numerical value of BULK CURRENT will be displayed /entered as 3 digits. For example, 1A
will be displayed / entered as “001”; 40A will be displayed / entered as “040”; 105A will
be displayed / entered as “105” and so on. The overall numerical value of the parameter is
changed digit by digit starting from the 1st digit on the left. On entering the first parameter
change screen, a curser will appear under the 1
st
digit and the cursor and the digit will be
blinking. Scroll to the desired numerical value for the 1
st
digit using Up and Down Keys. Press
the Enter Key
momentarily
to write the desired numerical value for the 1
st
digit. The curser
will automatically move to the 2
nd
digit on the right and 2
nd
digit and the curser and the digit
will be blinking. Scroll to the desired numerical value for the 2
nd
digit with the help of Up and
Down Keys. Then, press the Enter Key
momentarily
to write the desired numerical value for
the 2
nd
digit. The overall numerical value of the parameter will be selected after scrolling to
the desired numerical value for the last digit. Now, press the Enter Key,
HoLD for 3 to 4 sec
and then release
. Process for writing the overall numerical value of the parameter into the
memory will be initiated – the screen will display message “WRITING…” followed by message
“WRITE SUCCESS”.
Please read Section 4.3.1 for example of programming a typical parameter – BULK CURRENT
i
inFo
1. When the numerical value for any individual digit is changed that makes the
overall numerical value of the parameter outside the programmable range, an
Exclamation Sign “!” will appear on the left of the display screen warning you
to correct the overall numerical value of the parameter to within the program-
mable range before writing the new overall numerical value of the parameter to
memory.
2. If, after scrolling to the desired numerical value for the last digit, the overall nu-
merical value of the parameter is out of the programmable range, the Exclamation
Sign “!” will continue to appear on the left of the display screen. If an attempt
is made to write this “out of range overall numerical value” into the memory (by
pressing and holding the Enter Key when the cursor is at the last digit), message
“OUT OF RANGE” will be displayed and the screen will go back to display the
originally stored value of the parameter.
Parameter set up procedure will have
to be re-started.
3. If there is some problem in writing to the memory, message “WRITE FAILURE” will
be displayed.
Parameter set up procedure will have to be re-started
.