9
Electrical connection
J1
+
Analogue output
G
Analogue output reference
J2
Sh
Shielded RS485 cable
G0
GND for RS485
A
Tx + / Rx + for RS485
B
Tx- / Rx- for RS485
J3
+24
Vac/dc
For Vac power supply, connect the second transformer wire
+24 V
AC/DC
For Vdc power supply, connect one of the two power wires, the device automatically recognizes whether this
is + or GND. For AC power supply, connect one of the two transformer wires.
J4
1A
NO contact for the warning/fault relay
2A
Common for the warning/fault relay
3A
NC contact for the warning/fault relay
J5
1B
NO contact for the alarm relay
2B
Common for the alarm relay
3B
NC contact for the alarm relay
J6
+
V+ for the output voltage provided for service
G
Service voltage reference
J7
/
Built-in version sensor connector
J8
/
Remote version sensor connector (connection not to be used for built-in products)
All external circuits connected to device shall be double or reinforced isolated from mains meet SELV and Limited
energy requirements according to clause 9.4 of UL61010-1 3rd edition.