24
Input register 102 : bits
Bit
Description
Long description
Fault
Service Port Error Code
0
No reply from SM
Yes
1 V
1
No reply from sensor
Yes
2 V
2
Preheating
From sensor, 1 during preheating
3
Reserved
Internal use only
4
Over range
Over range from sensor
5 V
5
Under range
Under range from sensor
Yes
3 V
6
Reserved
For internal use only
7
Reserved
For internal use only
8
Reserved
For internal use only
9
Reserved
For internal use only
10
ServiceDue
SM reporting service due
11
SensorExpired
SM reporting sensor expired
12
N/A
13
Reserved
For internal use only
14
Reserved
For internal use only
15
N/A
Function 05 Write Single Coil & Function 01 Read Coils
Address Register name Short description Medium description Long description Max
value
Min
value
Unit of
meas.
Modbus
Bit pos.
Modbus
length
Default
value
401
ServiceDue
Service needed
Maintenance
indicator
(Including
calibration)
1 = maintenance
required
1
0
0
1
0
402
Acknowledge Acknowledge
Manually
acknowledge
warning or alarm
Write 1 to
acknowledge
1
0
0
1
0
403
RelayFailSafe Relay FailSafe
Relay in failsafe
mode
1 = Relay in failsafe
mode
1
0
0
1
0
404
RelayWF
Relay WF
Warning relay used
as fault
1 = Warning relay
used as fault
1
0
0
1
0
405
Acknowledge
Warning
Acknowledge
warning
Manual/automatic
warning
acknowledgement
setting
1 = automatic
reset; 0 = manual
reset
1
0
0
1
0
406
Acknowledge
Alarm
AcknowledgeAla
rm
Manual/automatic
alarm
acknowledgement
setting
1 = automatic
reset; 0 = manual
reset
1
0
0
1
1
407
ZeroCalibrati
on
Zero calibration
Start zero
calibration
command
1 = start calibration 1
0
0
1
1
408
SpanCalibrati
on
SpanCalibration
Start span
calibration
command
1 = start span
calibration
1
0
0
1
0
409
FactoryReset Reset
Reset the detector
to the factory
settings
1 = restore factory
settings
1
0
0
1
0
Содержание GLACIAR MIDI
Страница 1: ...GLACI R MIDI Gas Leakage Detector for commercial and industrial applications USER MANUAL...
Страница 5: ...5 2 2 Physical dimensions Built in version Remote version...
Страница 29: ...29 5 4 1 Diagram of the calibration procedure...
Страница 30: ...30 5 4 2 Operation of the registers for calibration...
Страница 38: ...38...
Страница 39: ...39...
Страница 40: ...40 Manufactured by Samon AB Modemgatan2 S 23539Vellinge Sweden www samon se...