17
4.6
Magnetic key for configuration
The device is supplied with a magnet for configuration. By placing it in the slot provided, the following functions can be
managed:
4.6.1
Bluetooth activation
After 5 seconds of exposing the magnet to the magnetic sensor, Bluetooth mode is activated. If Bluetooth is already on,
after 5 seconds of exposure Bluetooth is deactivated.
Bluetooth mode is automatically deactivated after 20 minutes of inactivity. Product operation in Bluetooth mode is
indicated by the rapid flashing of the green LED.
Bluetooth Activation is used to set up the product on installation and/or enter maintenance mode. When in this mode,
the alarms (if present) are disabled until the normal operating mode is restored, deactivating Bluetooth.
4.6.2
Alarm/warning management
If a warning or alarm is active, after 2 seconds of exposure, the alarm will be acknowledged and deactivated. If gas is still
present, the detector will enter alarm or warning mode as usual, after a 10-second delay.