Sammode SA
N° : 415 034 rév. H
24, rue des Amandiers – F 75020 Paris
6/12
Décembre 2015
EN
1
- 1 -
8
Good
Foreword
The following instructions must be read, among others, together with the Standards EN 60079-17 (Inspection and
maintenance of electrical installations in hazardous areas (other than mines)), EN 60079-14 (Electrical apparatus for
explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)),
EN 60079-19 (Repair
and overhaul for apparatus used in explosive atmospheres), the by-laws, decrees, orders, laws,
directives, implementation circulars, other relevant standards, state of the art and any other document regarding the
relevant installation site. Sammode cannot and will not be liable if these standards are not complied with. The user shall
be fully aware of the electrical hazards as well as the physical and chemical characteristics of the dusts to be found in
the installation. This shall include, among others, the checking of the compatibility between the surface temperatures of
the luminaire and the ignition temperatures of these dusts in particular. The same applies to combustible gas, vapours
or mists.
This luminaire is meant for areas where potentially explosive dust and/or gas atmospheres may be present:
Area 21, Area 1
These area definitions may be as follows:
-
Area 21: Location where an explosive atmosphere, taking the form of a combustible dust cloud in the air, is liable
to occasionally gather under normal operating conditions.
-
Area 1: Location where an explosive atmosphere, taking the form of a combustible gas cloud in the air, is liable to
occasionally gather under normal operating conditions.
Determination and delimitation of these areas fall within the responsibility and competence of the person in charge of
the site.
Instructions for a hazard-free installation (to be carried out by trained staff)
1 Installation
Any work on the luminaire should be carried out when voltage is off.
1.1
Position the fixing straps
alone.
1.2 – Prior to the installation of the luminaire in its fixing straps
:
a) loosen the screw in the middle
in order to free the internal gear tray
,
b) remove the mobile flange
,
c) From this same side, pull the tray as it is shown in “-figure 1-“ (Pull
no more than 20 cm). Mount the fluorescent tube(s) on the sockets,
d) connect (See § 2),
e) To close the lighting apparatus, push the tray and put it under the fastener
1.3 – Install the unit in its straps
after fastening them as described in §
1.1.
1.4 – Position the mobile flange
so that it properly covers the seal
.
1.5 – Tighten the middle screw
assuring that the mobile flange
properly sits on the seal
.
Fully tighten the middle screw
to
ensure the required tightness of the unit. Avoid excessive tightening
(a tightening torque of 1,7 N.m + 0/- 0.1 is to be applied to the
middle screw
). To be sure it is well locked, compare the
deformation of your joint (under the screw
) with the following
photos:
1.6
Tighten the cable gland (tightening torque of 5 N.m +/- 0.5).
1.7
Rotate the unit in order to position it in the lighting direction as desired by opening the fixing straps
- 2 -