3. Wiring process
The photovoltaic inverter wiring is as shown above.
Warning :
National Electrical Code (NEC) requires that the inverter be
connected to a dedicated circuit and no other outlets or device may be
connected to this circuit. See NEC Section 690-64(b)
Warning :
Follow local electrical codes and the National Electrical
Code (NEC), ANSI/NFPA 70. Use copper conductors only with
minimum 12 AWG, 105
℃
, 600V
wire for all connections with the
Soleil 2000.
Power cable selection
AC wire:
Black copper wires of 12 AWG
or above should be used for alternate current
output.
Ground wire:
For enclosure grounding, green or yellowish green copper wires of
12AWG or above should be used.
DC wire:
For input to the unit from solar panels, the cross section area is dependent on the
length of the wire. Identifiable colored copper wires of 12 AWG or above, for both positive
and negative power supplies should be used.