INSTALLATION
Location, mounting and safety
The charger is required to be installed in a safe, well ventilated and dry location. Please
see the details given under “Important Safety Instructions“ on page 2.
With the help of 4 screws, mount the charger on a vertical bulkhead with the output
terminal side facing down.
Output connectors
A terminal block with tubular, screw down type of terminals is used for output connection.
The diameter of the tubular holes is as follows:
SEC-1215E
4mm
SEC-2415E/ SEC-1230E
6mm
CAUTION!
For firm connection when using stranded cable, crimp / solder”pin” style terminal on the charger
end of the DC cables used for connecting to the battery / other DC loads.
Cables
To avoid polarity errors and possible damage, never use wires of only one color. Use red
insulated wire(s) for positive connection(s) and black for negative connection(s)
Recommended DC cable sizes are given below. The length in feet is the length of the pair of
the positive and negative DC cables from the charger to the battery / other DC load:
Length of the pair of the
SEC-1215E/ SEC-2415E
SEC-1230E
Positive & negative cables
0 to 1,80 mtr
6 Mmq
10 Mmq
1,80 to 3 mtr
10 Mmq
16 Mmq
3 to 6 mtr
16 Mmq
25 Mmq