SYMPTOMS WHEN THE CHARGER IS POWERED AND IS BEING USED AS A
DC POWER SUPPLY/UPS
THE VOLTAGE DROPS WHEN LOAD IS SWITCHED ON
The load is trying to draw current more than the current limit value of the charger
(the current limit value is the maximum specified charging amps). Once the load current
reaches the current limit value, the current limit circuit is activated and the output voltage drops.
Some loads like motors, compressors, incandescent lamps, halogen lamps, heating elements,
relays, coils, capacitors etc. draw very large in rush/starting currents which may reach up to
10 times their normal operating currents. Ensure that the starting / in rush current or the
maximum operating current of the load is lower than the current limit value of the charger.
INTERNAL FUSE RATINGS
Both the AC side and DC sides have fuses that are located inside the charger. Disconnect the
AC power when checking or changing the fuses. Open the charger as follows:
1 Remove the 4 screws on the ammeter side of the topcover
2 Gently slide the top cover out by about 5 - 8 cm. (CAUTION ! The top cover will
be restrained from fully sliding out by the wires connecting the ammeter, LED and fan)
3 The fuses will now be accessible
FUSE RATINGS:
SEC-1215E SEC-1230E
SEC-2415E
230VAC INPUT
2A/ 250V
4A/ 250V
4A/ 250V
DC OUTPUT
20A/32V
2x20A/32V
2x10A/32V