Charging more than one bank of batteries 

CAUTION! When charging more than one bank of batteries at the same time using 3 Stage 
Charging, ensure that the batteries in the banks are in a similar discharged condition.If one 
bank is completely discharged and another is almost fully charged, the bank that is fully charged 
will be subjected to over charge condition during the time when the charger remains in Boost 
Stage for charging the completely discharged bank.

 

Powering other DC Loads 
The charger can be used as a power supply or as a DC UPS. For both these applications, 
first set the Dip Switch to “Battery with load“.(See under” Selecting the Type of Battery and 
Charging Stages“ on page 4 ) 

To use as a power supply, first switch off the DC load. Connect the DC load between the 
common negative terminal and one of the three positive terminals. Ensure that the maximum 
current drawn by the DC load is below the maximum current rating of the charger. 
Switch on 
the charger and then the DC load 

In a DC UPS (Un-interruptible Power Supply),the charger 
simultaneously powers the DC load as well as the battery. As long as the AC power to the 
charger is available and the charger isworking normally, the charger will supply the DC load as 
well as charge/float the battery.  In case the AC power fails or if the charger stopsworking, the 
battery will automatically power the DC load. As soon as the AC power to the charger is 
restored, the DC load will once again be fed by the charger and at the sametime the battery 
will be recharged. CAUTION! Please ensure that the sum of the current drawn by the DC load 
and the current desired for charging the battery is less than the maximum current capacity of 
the charger. To use as a DC UPS, first switch off the DC load and connect it to the battery. 
Now connect the battery as explained above under ”Charging a Battery outside theVehicle“ 
on page 9. Switch on the charger and then switch on the DC load 

10

Содержание SEC - 1215E

Страница 1: ...SEC 1215E SEC 1230E SEC 2415E Model No AUTOMATIC BATTERY CHARGER OWNER S MANUAL Please read this manual before operating your charger...

Страница 2: ...IMPORTANT SAFETY PRECAUTIONS 2 DESCRIPTION AND FEATURES 3 CHARGING STAGES 4 PROTECTIONS 5 INSTALLATION 6 CHARGER OPERATION 7 8 9 10 TROUBLESHOOTING 11 12 INTERNAL FUSE RATINGS 12 SPECIFICATIONS 13 WAR...

Страница 3: ...e compartment as batteries ChargerRelated r Do not operate the charger in a closed in area or restrict ventilation in any way Install in a well ventilated cool dry place r The charger must not be oper...

Страница 4: ...rolled cooling fan SEC 1230E SEC 2415E r Protectionsagainst short circuit overcurrent reverse battery connection and over temperature over temperature for SEC 1230E and SEC 2415E r Can be used as a po...

Страница 5: ...e threshold of battery gassing termed boost or absorption voltage the charger automatically switches over to Stage 2 Boost or Absorption Stage The value of this voltage depends upon the type of batter...

Страница 6: ...draw a higher current than these limits the output voltage of the unit will start to drop The unit will automatically recover when the overload condition is removed Reverse Battery Connection Cut Off...

Страница 7: ...1230E 6mm CAUTION For firm connection when using stranded cable crimp solder pin style terminal on the charger end of the DC cables used for connecting to the battery other DC loads Cables To avoid p...

Страница 8: ...ng Always change the Dip Switch setting when the charger is off i e after disconnecting the charger from the AC input power NOTE The voltages are for a temperature of 80 Degrees F DIPSWITCH SETTINGS S...

Страница 9: ...nsisting of more than one battery in parallel is to be charged make sure that their negatives are connected to the common negative terminal of the charger and their positives are connected to the same...

Страница 10: ...frame or engine block which is away from battery Do not connect to carburetor fuel lines or sheet metal body parts 6 For a positive grounded vehicle connect the negative black DC cable from the charge...

Страница 11: ...current drawn by the DC load is below the maximum current rating of the charger Switch on the charger and then the DC load In a DC UPS Un interruptible Power Supply the charger simultaneously powers t...

Страница 12: ...S GETTING OVER CHARGED OR BOILS The charger is also feeding other DC load s in parallel with the battery The Dip Switch is not selected for Battery with Load Change Dip Switch setting to Battery under...

Страница 13: ...y reach up to 10 times their normal operating currents Ensure that the starting in rush current or the maximum operating current of the load is lower than the current limit value of the charger INTERN...

Страница 14: ...1 13 8 VDC 13 8 VDC 27 6 VDC Output Amps 15 A 30 A 15 A Operating Temp Range 0 40 C 0 40 C 0 40 C Weight 2 35 kgs 3 1 kgs 3 1 kgs Housing Dimensions LXWXH mms 215x213x80 273x213x80 273x213x80 Protect...

Страница 15: ...rmed only by the Warrantor Any attempt to remedy the defect by anyone other than the Warrantor shall render this warranty void There shall be no warranty for defects or damages caused by faulty instal...

Страница 16: ...www samlex com www samlex solar com...

Отзывы: