45
SAMLEX AMERICA INC. | 45
a) When NOT using external 1-Wire or 2-Wire ON/OFF Control: By switching OFF
the 3-Position Rocker Switch (1,
f
ig 6.1a) to center position marked “O” / “OFF”
b) When using external 1-Wire or 2-Wire ON/OFF Control: By Switching OFF the
inverter by (i) opening the switch or the relay contact in 2-Wire ON/OFF Control
(fig 8.2a) or (ii) opening the switch or relay contact in 2-Wire ON/OFF Control using
switched DC voltage (fig 8.2b) or (iii) opening the switch or relay contact in 1-Wire
o N/off Control using switched DC voltage from the battery supplying the inverter.
SECTION 10 |
Protections
10. PROTECTIONS
The inverter has been provided with protections detailed below:
10.1 POWER SURGE / OVERLOAD / SHORT CIRCUIT SHUT DOWN
i
INFO
Please refer to
of Active Power (Watts), Apparent Power (VA) and
Power Factor (PF) at Section 2.1. In the explanation below, the values of Power
are expressed in Apparent Power in VA. Corresponding Active Power (Watts, W)
will depend upon the type of load (Resistive or Reactive) and its Power Factor
(Power Factor may range from 1 to 0.5). Please note the following:
•
Active Power (Watts) = Apparent Power (VA) x Power Factor (PF).
•
For resistive type of loads, the Power Factor = 1 and hence, Apparent
Power (VA) = Active Power (Watts, W)
•
For reactive types of loads, the Power Factor will be < 1 (up to 0.5) and hence,
the Active Power (Watts, W) will be less than the Apparent Power (VA)
The AC output voltage will shut down due to overload and short circuit conditions as follows:
POWER SURGE CONDITION: When the AC output current tries to exceed around 200%
of the rated value, output current limiting is carried out instantly resulting in drop in
the AC output voltage (the drop is proportional to the load impedance). Surge Power of
200% will, thus, be provided for < 8 ms every half cycle. If this situation continues for 2
to 2.5 sec Overload Condition is activated.
OVERLOAD CONDITION: If there is a continuous overload of 110% to 115% for 2 to 3
sec, the output voltage will be shut down. Red LED marked “OVERLOAD” (3,
f
ig 6.1a)
will turn ON, the Green indication light on the GfCI outlet will be OFF and buzzer alarm
will sound. The Green LED marked “POWER” (2, Fig 6.1a) will continue to be lighted.
The unit will be latched in this shut down condition and will require manual reset.
SECTION 9 |
Operation
48 | SAMLEX AMERICA INC.
SECTION 11 |
Troubleshooting Guide
ISSUE
POSSIBLE CAUSE
REMEDY
When switched ON, the
Green LED marked "POWER"
(2, Fig 6.1a) does not light.
Buzzer is OFF. There is no AC
output voltage.
There is no voltage at the
DC input terminals
• Check the continuity of the battery
input circuit.
• Check that the internal/external battery
fuses are intact. Replace if blown.
• Check that all connections in the battery
input circuit are tight.
Polarity of the DC input
voltage has been reversed
that has blown the exter-
nal / internal DC side fuses
(
Note: Reverse polarity
may cause permanent
damage
. Damage caused
due to reverse polarity is
not covered by warranty)
• Check external and internal fuses. Internal
fuses may be soldered and may not be easily
replaceable. Replace fuses. If unit does not
work, call Technical Support for repair.
Low AC output voltage
(No buzzer alarm).
Low DC input voltage at
the inverter terminals and
the load is close to the
overload limit of 110%
(3300W).
• Check that the battery is fully charged.
Recharge, if low.
• Check that the battery cables are thick
enough to carry the required current over
the required length. Use thicker cables, if
required.
• Tighten connections of battery input circuit.
• Reduce load to below 3000W.
Buzzer alarm is sounded when
load is switched ON. Voltage
at DC input terminals reads
between 10 to 10.7V for 12V
versions and between 20 to
21.4V for 24V versions. The
Green LED marked "POWER"
(2, Fig 6.1a) is lighted. Indica-
tion light on. AC output
voltage is available.
DC input voltage is less
than 10.7V for 12V
versions and less than
21.4V for 24V versions.
• Check that the battery is fully charged.
Recharge, if low.
• Check that the battery cables are thick
enough to carry the required current over
the required length. Use thicker cables, if
required.
• Tighten connections of the battery input
circuit.
Buzzer alarm is sounded
when load is switched ON.
Voltage at the DC input
terminals reads below 10V for
12V versions and below 20V
for 24V versions. The Green
LED marked "POWER" (2, Fig
6.1a) is lighted. GREEN indica-
tion light on. There is no AC
output.
Shut-down due to low
DC input voltage - Less
than 10V for 12V versions
and less than 20V for 24V
versions.
• Check that the battery is fully charged.
Recharge, if low.
• Check that the battery cables are thick
enough to carry the required current over
the required length. Use thicker cables, if
required.
• Tighten connections of the battery input
circuit.
• The AC output voltage will switch ON au-
tomatically when the DC input voltage rises
to 11.5V ± 0.
3
V for 12V version and 23V
± 0.
5
V for 24V version.
44
45
Содержание PST-300S-12E
Страница 102: ...102 51 OPMERKINGEN 102...
Страница 153: ...153 HINWEISE 153...
Страница 184: ...184 SECTION 8 Installation 31 NOTE Dimensions en mm Fig 8 1 Dimensions g n rales rainures de montage du PST 300S 184...
Страница 204: ...204 51 NOTES 204...
Страница 255: ...255 51 NOTAS 255...
Страница 256: ...256 256 www samlex com www samlex solar com 256...