8.4.5 Recommended Sizes of Battery Cables and Fuses
Sizes of cables and fuses are shown in Table 8.2. Sizing is based on safety considerations
in UL-458, NEC-2014 and ISo -10133. Please refer to “Notes for Table 8.2” for
details.
Table 8.2 Recommended Sizing of Battery Cables
and External Battery Side Fuse
Model No.
Maximum
Continu-
ous DC
Input
Current
Maximum
External
Battery
Fuse Size
Minimum cable size
(See Note 4)
< 1,50 m
m
2
> 1,6-3 m
m
2
PST-300S-12
E
360A
400-500A
95
120
50
PST-300S-24
E
180A
300A
70
SECTION 8 |
Installation
36 | SAMLEX AMERICA INC.
against short circuit. Amp rating of the fuse is based on the following considerations:
a) Not less than the Maximum Continuous DC Input Current (Column 2)
b) Closest Standard Ampere Rating of fuse has been used - Refer to NEC-2014
(National Electrical Code) - Section 240.6(A)
c) Where Standard fuse Rating does not match the required Ampacity (Col-
umn 2), the next higher Standard Rating of the fuse has been used - Refer to
NEC-2014 (National Electrical Code) - Section 240.4(B)
d) type of fuse: fast-acting, Current Limiting, UL Class T (UL Standard 248-15)
or equivalent
5) Samlex America, Inc. makes 4 Models of generic / universal Inverter Installation Kits to cov-
er installation requirements of a wide power range from 600W to 3500W for 12V invert-
ers and from 1200W to 7000W for 24V inverters. Please note that the Inverter Installation
Kit that has been recommended in Column (8) may include thicker wire size / correspond-
ingly bigger fuse size than those recommended in Table 8.2. This is acceptable.
fuse in the battery circuit is primarily required for protection against short circuit in
the battery cable run. The size of this fuse has to be equal to or larger than the maxi-
mum DC input current of the inverter at Column (2). further, the Amp rating of the
fuse used for protecting a battery cable against short circuit has to be lower than the
Ampacity of the cable so that the fuse blows before the cable insulation is damaged
due to overheating as a result of fault current higher than the Ampacity of the cable.
The Amp ratings of fuses provided with the Inverter Installation Kits are lower than
the wire size provided with the Kit.
The Kits come with 10ft length of cables to cover battery to inverter distance of up to
10 ft. If the actual cable routing distance from the battery to the inverter is less than
10ft, please cut-off the extra length of cables. This will result in reduction in the over-
all resistance of the cable / reduction in voltage drop and consequently, will improve
the efficiency of the inverter system
8.4.6 Dc input connection
The DC input terminals for battery connection (14 & 16 in fig. 6.1c) have nut and bolt con-
nection - bolt size is 5/16" (18 Threads per Inch). Use ring tongue type of terminals on the
wire ends to fit 5/16" bolt size.
8.4.7 Reducing RF interference
Please comply with recommendations given in Section 3 - "Limiting Electromagnetic
Interference".
34
35
Содержание PST-300S-12E
Страница 102: ...102 51 OPMERKINGEN 102...
Страница 153: ...153 HINWEISE 153...
Страница 184: ...184 SECTION 8 Installation 31 NOTE Dimensions en mm Fig 8 1 Dimensions g n rales rainures de montage du PST 300S 184...
Страница 204: ...204 51 NOTES 204...
Страница 255: ...255 51 NOTAS 255...
Страница 256: ...256 256 www samlex com www samlex solar com 256...