14 

 

3.

 

Charge status bar. Gives a rough indication of the charging progress, see below : 
 
                    LED 3a  :  100% full (ready) 
                    LED 3b  :  80% full 
                    LED 3c  :  50% full 
                    LED 3d  :  empty 
 

4.

 

Power on, off, charger only switch. See chapter 4.1 for more explanations. 

 

4.2.1.   Error indications 

 
When the so called mode indicator LEDs are blinking red, an error has been detected. Each 
mode indicator LED can either blink red individually, or combined along with one or more 
other mode indicator LEDs. There are five different error indications, each with their own 
blinking pattern : 
 
  One flash in a row    :  Battery related error (too low or too high battery voltage, too 
                    low or too high battery temperature, too high battery ripple  
                    voltage, battery defect) 
  Two flashes in a row   :  AC overload error (AC load requires too much power from the 
                    inverter, AC output short circuit) 
  Three flashes in a row  :  High temperature error (Powersine Combi shuts down on high 
                    temperature) 
  Four flashes in a row  :  Device error (an error has occurred inside the Powersine    
                    Combi. Please return for service) 
  Five flashes in a row   :  Charge program error (only for ‘charger on’ indicator LED). 
                    Charge program selection set to Custom, while custom made  
                    charge program contains an error or time-out. 
 
The Powersine Combi will mostly recover from an error mode automatically when the cause 
of the error has been resolved. However, when an error has occurred due to a high battery 
ripple voltage or an AC transfer switch overcurrent, the Powersine Combi needs to be 
switched off and on again manually (manual restart). The Powersine Combi also needs to be 
restarted manually, when too many battery or overload errors have occurred within a short 
period of time.  
 

4.3  Programmable Alarm relay 

 
The Powersine Combi is equipped with one or two (depending on model) programmable 
potential free alarm relays. Standard, this relay (or relay 1 on PSC2000-3500 models) will be 
activated when the unit shuts down and jumps to an error mode. The alarm relay de-
activates again when the error has been resolved and the Powersine Combi is running in 
normal operating mode again.  
 
 
 

Содержание PSC1600-12-60

Страница 1: ...800 24 35 PSC2500 24 50 PSC3500 24 70 Model No SINEWAVE INVERTER CHARGER Manual Gebruiksaanwijzing Benutzerhandbuch Manuel Utilisateur Manual Para Utilizador Please read this manual before operating y...

Страница 2: ...SSES DAMAGES COSTS OR EXPENSES WHETHER SPECIAL DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE...

Страница 3: ...12 4 1 Operating the Powersine Combi 12 4 2 Powersine Combi LED indicators and error modes 12 4 2 1 Error indications 14 4 3 Programmable Alarm relay 14 4 4 Trigger input 15 4 5 Load requirements in i...

Страница 4: ...of this owner s manual is to provide explanations and procedures for operating and configuring the Powersine Combi For installing the Powersine Combi a separate installation guide is included The inst...

Страница 5: ...ting the inverter The connected loads are now supplied again by the grid generator without any interruption Additionally the Powersine Combi offers features like AC Input Power Boost which temporarily...

Страница 6: ...gured in SAMLEX Dashboard When DIP switch 1 is set to OFF Local again DIP switch 2 up to 7 or 9 are overriding the corresponding parameter settings previously made in SAMLEX Dashboard The parameters t...

Страница 7: ...Parameter AC input voltage range transfer switch Value 180V 270V Description Input voltage range which is accepted by the Powersine Combi for feeding through to the connected load Two AC undervoltage...

Страница 8: ...nd Dashboard Parameter AC input fail sensitivity Value Normal Description This parameter can be set to Very Low Low Normal High and Very High The value of this Parameter decides how fast the Powersine...

Страница 9: ...w During step 3 of the installation guide you can alter the factory settings of the DIP switches to change the functionality of the Powersine Combi on a few points For additional information about the...

Страница 10: ...age 13 3V 26 6V programmable Factory setting OFF AC Input Power Boost ON AC Input Power Boost on OFF AC Input Power Boost o Factory setting ON Models PSC1600 1800 Bypass remote switch Bypasses the rem...

Страница 11: ...e serious damage to your batteries and or connected battery loads Always consult your battery s documentation for the correct charge voltage settings 2 When charging and discharging lithium batteries...

Страница 12: ...lease the AC transfer switch and activate the inverter again All this happens so fast that the connected load will not be disturbed When switched to Off the Powersine Combi is completely shut down and...

Страница 13: ...as well as the status of each different mode see explanation below charger on LED Off not charging On green charging On blinking red error see chapter 4 2 1 On red charger disabled inverter on LED Off...

Страница 14: ...s in a row Device error an error has occurred inside the Powersine Combi Please return for service Five flashes in a row Charge program error only for charger on indicator LED Charge program selection...

Страница 15: ...ce the Powersine Combi to switch to inverter mode All this can be configured in SAMLEX Dashboard The PSC1600 1800 models are equipped with one trigger input while the PSC2000 3500 models are equipped...

Страница 16: ...80 full indicator will be lit This stage will return the final 20 of charge to the battery The output voltage is kept at a constant level and the charge current decreases as a function of the battery...

Страница 17: ...ements must be read carefully When the battery temperature sensor is installed the charger automatically compensates the charge voltages against battery temperature except when set to Lithium This mea...

Страница 18: ...button on the bottom side of the unit see images below for 3 seconds until all charge status indicators start flashing Models PSC1600 1800 Models PSC2000 3500 The Powersine Combi will allow a maximum...

Страница 19: ...r mode is not working AC transfer switch does not activate either The AC input voltage or frequency are out of range or too unstable Make sure that the AC input voltage is between 185V 270V and the fr...

Страница 20: ...eck the DC system for an external source that pushes the battery voltage too high Too high ripple voltage on DC input manual restart needed Check battery wire connections Decrease battery cable length...

Страница 21: ...cy borders Make sure that the AC input voltage falls within 185V 270V and 45Hz 65Hz All mode indicator LEDs inverter on charger on and AC in are blinking red twice per second manual restart needed Max...

Страница 22: ...rogram contains go to error condition for example when a charge stage takes too much time If none of the above remedies will help solving the problem you encounter it s best to contact your local SAML...

Страница 23: ...bled Yes Protections high low battery voltage high temperature overload short circuit high ripple voltage and low AC input voltage DC connections Two wires length 1 5 meters 35mm2 AC connections Screw...

Страница 24: ...led Yes Protections high low battery voltage high temperature overload short circuit high ripple voltage and low AC input voltage DC connections M10 bolt terminals AC connections Screw terminals Enclo...

Страница 25: ...bled Yes Protections high low battery voltage high temperature overload short circuit high ripple voltage and low AC input voltage DC connections M10 bolt terminals AC connections Screw terminals Encl...

Страница 26: ...of the product and product malfunctioning Since SAMLEX cannot control the use and installation according to local regulations of their products the customer is always responsible for the actual use of...

Страница 27: ...2500 24 50 PSC3000 12 120 PSC3500 24 70 Conforms to the requirements of the following Directives of the European Union EMC Directive 2004 108 EC The above product is in conformity with the following h...

Страница 28: ...www samlex com www samlex solar com...

Отзывы: