ENGLISH
10. ALARM MESSAGES
SCREEN
DESCRIPTION
If the sense of the cycle of the input voltages R, S, o, T (SA687.xx) is
inverted, the display shows the following message.
KLIXON
MOTOR
If the internal temperature of motor exceeds the KLIXON thermal threshold,
the motherboard will turn off the motor and
the display will show the
following message.
DATA
LOGGER
If the current absorbed by the motor exceeds that adjusted in the setup,
the
motherboard will turn off the motor and
the display will show the following
message.
If the current absorbed by the motor is lower than the current set in the setup,
the motherboard will turn off the motor and the display will show the following
message.
If the supply voltage drops below the minimum voltage and this condition
persists for 5 seconds the alarm is activated, the motor is no longer powered
and you will see the following message. If the voltage is within the set range
and stays there for 60 seconds, the motherboard will automatically reset the
alarm.
If the supply voltage exceeds the maximum voltage and this condition
persists for 0.5 seconds the alarm is activated, the motor is no longer
powered and you will see the following message. If the voltage is within the
set range and stays there for 60 seconds, the motherboard will
automatically reset the alarm.
If the motherboard detects the absence of one of the three phases R, S, or T,
(SA687.xx), the display shows the following message.
ALARM
MAXIMUM LEVEL
MINIMUM PRESSURE
PRESS RESET
If the pressure in the system falls below the value set in the MINIMUM
PRESSURE parameter of the setup, the motherboard will turn off the motor
and the display will show the following message.
If the water level in the tank exceeds the level set in the ALARM LEVEL
parameter, the display will show the following screen.
All alarms are automatically reset except for the maximum current which is reset by pressing the
button for 2 seconds.
In the motherboard, when any type of alarm is generated, three outputs are activated, two 12Vdc
outputs respectively for siren and flashing lamp and one with pure contact relay.
By means of the button it is possible to silence the siren output which will remain deactivated
until a new alarm is generated.
41
MAXIMUM CURRENT
PREMI RESET
MINIMUM CURRENT
PRESS RESET
ALARM
MINIMUM VOLTAGE
ALARM
MAXIMUM VOLTAGE
ALARM
LACK OF PASHE
ALARM
REV. RST PHASES
If the number of starts per hour surpasses the preset limit, the motherboard
will stop the motor and the display will show the following screen.
MAX STARTS MOT.
PRESS RESET
Содержание MULTIPLUS 1 SA684 Series
Страница 24: ......