FREQUENT PROBLEMS
CAUSES
OPERATION
Application SEWAGE/CLEAN WATER:
FLOAT SWITCHES OFF status
with full tank
Application COS :
φ
EXTERNAL COMMAND OFF
with empty tank
Ceck the functionality of the float switches
and replace if necessary
Possible failure of the float switch
Ceck the functionality of the float switches
and of the cable and replace if necessary
Possible failure of the float switches
or connection cable interrupted
Feed the control panel respecting
the input voltage
Set the switch on 1
Connect the flat cable from the motherboard
to the display
Switch set on 0
MAXIMUM CURRENT alarm
Maximum current set on the setup less
than that absorbed by the motor
Motor blocked or damaged
Application 4-20mA meters:
The displayed level
in meter is wrong
Clean carefully the piezoresistive probe
or
replace if necessary
Possible obstruction or failure of the
piezoresistive probe 4-20mA
9.
TROUBLESHOOTING AND PROPOSED SOLUTIONS
Application 4-20mA bar:
Pressure value in bar displayed
in the wrong display
Clean carefully the pressure transducer
or
replace if necessary
Possible obstruction or failure of the
4-20mA pressure transducer
Display off
N
o supply
The flat cable inside the control panel
is not connected
Set manually the maximum current the 25%
more than the nominal value
Disconnect the motor and be sure
it is working properly
40
Содержание MULTIPLUS 1 SA684 Series
Страница 24: ......