22
SALICRU
t
Parameter 1:
Adjustable codes. For more information consult Tab. 8.
t
Parameters 2 and 3 are the configuration or value options
for each settings menu.
Select with buttons
‘ ’
or
‘ ’
to modify the menus
or parameters.
All of the parameter settings are saved when the
UPS is completely shut down and provided that it
has connected batteries, whether internal or external.
If a complete shutdown is not carried out, the setting will
not be saved to the memory.
7.3.2. Settings.
Tab. 8 shows a summary of parameter 1’s adjustable codes for
each operating mode and Fig. 16 shows the structure of the
menu tree with the operating mode for the settings.
Code
Description
Mode
No
output
AC and
batteries
ECO and
battery
test
01
Output voltage.
YES
-
-
02
Programmable output state.
YES
YES
YES
03
Programmable output configuration.
YES
YES
YES
04
Backup limitation configuration.
YES
YES
YES
05
Battery pack Ah configuration.
YES
YES
YES
06
EPO logical configuration.
YES
YES
-
Tab. 8.
Parameter 1 adjustable codes list.
7.3.2.1. Ah configuration of parameter ‘05’.
t
Standard models are configured with factory default
settings, so it is not necessary to perform any actions to
adjust this parameter.
For extended backup and B1 models, however, it is
necessary to adjust the value to the total capacity of the
battery pack. Any alteration of the battery pack will entail a
readjustment, so it will be necessary to adapt the value in
the event of future expansions.
t
There are basically two reasons to perform the adjustment
without it affecting the correct functioning of the device if it
is not done, although it is more than recommended:
a.
The charging current of the batteries is directly related to
the capacity of the battery pack.
The charger will adapt the charging factor automatically
according to the value of the total capacity entered, up
to the maximum of the current that is possible.
This results in faster charging and therefore greater
availability and more immediate backup in the event of
frequent mains failures.
b.
Entering the value in Ah is vital for the control to be able
to calculate and show the backup available on the LCD
display, without further alterations.
The settings values are determined as follows:
1.
Devices with backup extension.
They are configured by a standard model plus the battery
module or modules. The capacity of the batteries of both
are indicated in the following Tab. 9 and Tab. 10.
Example for an SPS.1500 ADVANCE RT2 and backup
extension module 6A0BU000003:
7 Ah + 14 Ah = 21 Ah (value for parameter 05).
UPS model
Internal batteries
Voltage (V)
Capacity (Ah)
SPS.800 ADVANCE RT2
24
7
SPS.1100 ADVANCE RT2
9
SPS.1500 ADVANCE RT2
48
7
SPS.2000 ADVANCE RT2
9
SPS.3000 ADVANCE RT2
72
Tab. 9.
Characteristics of batteries in standard devices.
Battery module
Code
Voltage (V)
Capacity (Ah)
6A0BU000001
24
14 (2 x 7)
6A0BU000002
18 (2 x 9)
6A0BU000003
48
14 (2 x 7)
6A0BU000004
18 (2 x 9)
6A0BU000005
72
Tab. 10.
Characteristics of batteries in modules.
2.
Device B1.
B1 models do not have batteries in the same box, so a
battery module will always be necessary or the user will
have them.
Example for an SLC 1500 ADVANCE RT2 B1 and three
backup extension modules 6A0BU000003:
(3 x 14 Ah) = 42 Ah (value for parameter 05).
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK