19
6. OPERATION.
6.1. START-UP.
6.1.1. Checks before start-up.
t
Make sure that all of the connections have been made
correctly, following the instructions on the labelling of the
device and in Chapter 5.
t
Check that the switch on the battery module or modules
is ‘Off’.
t
Make sure that all loads are ‘Off’.
Shut down the connected loads before starting the
UPS and start the loads, one by one, only when the
UPS is running. Before shutting down the UPS, check that
all of the loads are ‘Off’.
t
It is very important to proceed in the established order.
t
For views of the UPS, see Fig. 1..Fig. 3.
6.2. UPS START-UP AND SHUTDOWN.
6.2.1. UPS start-up with mains voltage.
t
Check that the power connection is correct.
t
Turn the battery module switch to ‘On’ (models B0 and B1).
t
Supply voltage to the device (turn the input protection on
the distribution board to ‘On’). If the board has an output
switch, turn it to ‘On’.
t
All of the models in this series have an input polarity
detector (phase-neutral), which activates a
modulated audible alarm every 2 seconds and displays the
message on the ‘
SF
’ display in the event of a fault.
When the circumstance arises, disconnect the plug from
the mains socket and rotate it 180º.
If the same alarm condition is maintained, it will be a two-
phase power line signal or installation without neutral
referenced to earth. Contact our
T.S.S.
or the distributor
before connecting loads to the output.
t
The fan or fans, depending on the model, will start to
function.
Then the main start screen will be displayed after a test of
the device.
t
Press the ON/MUTE button for more than 2 seconds, the
audible alarm will sound for 1 second, the UPS will start up
and an automatic battery test lasting 10 seconds will begin.
t
After a few seconds, the UPS will be in ‘Normal mode’.
If the mains voltage is incorrect, the UPS will switch to
‘Battery mode’, without interrupting the power supply at
the output terminals.
t
Start the load or loads, making sure that the rated power of
the device is not exceeded.
6.2.2. UPS start-up without mains voltage.
t
If it has a distribution board, turn the input and output
protections to ‘On’.
t
Turn the battery switch to ‘On’ (B0 and B1).
t
Press the ON/MUTE button for more than 2 seconds, the
audible alarm will sound for 1 second and the UPS will start up.
The fan or fans, depending on the model, will start to
function.
Then the main start screen will be displayed after a test of
the device.
t
After a few seconds, the UPS will be in ‘Battery mode’,
meaning that its charge level and therefore available
residual backup, as well as the risks associated with
operating in this mode, must be taken into consideration.
If the mains voltage returns, the UPS will transfer to
‘Normal mode’ without interrupting the power supply at
the output terminals.
t
Start the load or loads, making sure that the rated power of
the device is not exceeded.
6.2.3. UPS shutdown with mains voltage.
t
Shutdown the load or loads.
t
Press the OFF/ENTER button for more than 2 seconds to
shut down the inverter. The audible alarm will sound for
1 second. The device is in Standby (no output voltage) and
charging batteries.
6.2.4. UPS shutdown without mains voltage.
t
Shutdown the load or loads.
t
Press the OFF/ENTER button for more than 2 seconds to
shut down the inverter. The audible alarm will sound for 1
second. The device will leave the output terminals without
voltage.
A few seconds later, the LCD screen turns off and the entire
device will be out of service.
t
To leave the assembly completely isolated, turn the input
and output switches of the board to ‘Off’.
SPS.ADVANCE RT2
UNINTERRUPTIBLE POWER SUPPLY (UPS)
USER'S MANUAL
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK