- 21 -
4.6.2.- Remote control connection (saving order).
• Never mind the structure, version and power of the equipment, there are three groups of two terminals for connecting, the
remote control or the saving order, and they are labelled in the equipment as «Remote Control».
• To order the flow dimming: Connect to the remote control terminals one of the normally open contacts of an astronomical clock
or timer. The saving level will start and remains meanwhile this contact is closed. To be installed by the client.
DO NOT
apply
voltage to these terminals, because they are free potential contacts.
4.6.3.- Output connection.
• Connect the cables coming from the distribution lines to the output terminals (2
*
), by respecting the phase rotation and
neutral stated in the labelling of the equipment and in the figures 12 and 13 of this manual.
• Either the light installatio existed before installing the
ILUEST
, or it were new, the load must be distributed correctly in order
to balance it among the phases.
CONNECTION DIAGRAM
R-S-T-N
INPUT
U-V-W-N
OUTPUT
IP/OP
R N U
ILUEST
IP/OP
S N V
IP/OP
T N W
REMOTE
R-S-T
CONTROL
CONNECTION DIAGRAM
R-N
INPUT
U-N
OUTPUT
ILUEST
IP/OP
R N U
REMOTE
CONTROL
Fig. 12 Three phase ILUEST connection with BM478*
Fig. 13 Single phase ILUEST connection with BM478*