![Salicru EQUINOX EQX2 3001-HSX Скачать руководство пользователя страница 75](http://html1.mh-extra.com/html/salicru/equinox-eqx2-3001-hsx/equinox-eqx2-3001-hsx_user-manual_3633299075.webp)
75
EN
5.3.5. AC ON-GRID and AC BACK-UP
output connection.
Before connecting to the grid, make sure that the voltage and
frequency of the grid meet the inverter's requirements. Please refer
to the technical parameters for more details.
This inverter includes a built-in residual current device (RCD).
If an external residual current device (RCD) is used, a type B device
must be used, with a trip current of 30 mA or more.
5.3.5.1. Warnings to consider during
the connection.
1.
A separate AC circuit breaker is required on the grid side and
on the battery side. No load should be connected directly to
the inverter.
2.
Before connecting the AC cable, make sure that both the AC
and DC sources are disconnected from the inverter.
3.
The EQX2-HSX series single-phase hybrid inverter connects to
a 230 V, 50/60 Hz grid.
4.
The AC cable and AC circuit breaker recommended for the
EQX2 HSX series 3~8 kW single-phase hybrid inverter are
shown in the table below:
Model
Outer diameter (mm
2
)
Cable diameter (mm
2
)
EQX2 3001-HSX
12-18
4-10
EQX2 4002-HSX
EQX2 5002-HSX
6-10
EQX2 6002-HSX
EQX2 8002-HSX
Tab. 15. Cable cross-sections.
5.3.5.2. Steps for connecting the AC ON-GRID
connector.
1.
Remove the housing (item number 4) from its packaging.
4
2.
According to Tab. 15 above, select an appropriate cable
and pass it through the cable gland on the housing labelled
ON-GRID. A hole must be drilled in the rubber gasket to allow
the bundle to pass, as shown in the following sequence:
ON-GRID
Cables Screw
cap
Insulation
Cover
ON-GRID
3.
Pull the insulation sleeve out of the AC bundle by about 50 mm,
and pull the insulation out the end of the L/PE/N cables by
about 8 mm, as shown Fig. 54.
8 mm
50 mm
Cable diameter:10-14 mm
Fig. 54. Stripping the AC cable.
4.
Remove the ferrules included in the accessory bag from the
AC ON-GRID connector and crimp them to the stripped ends of
the L/PE/N cables with an approved tool to ensure an optimal
connection.
5.
Remove the AC ON-GRID connector from the accessory bag.
6.
Insert the ends of the three cables into the corresponding
holes on the connector: yellow-green cable into the PE port,
phase into the L port and neutral into the N port. Make sure
the cables reach the back of the connector and screw them
in tightly. Pull slightly on the cable to check that it is properly
connected.
7.
Connect the AC ON-GRID connector to the AC ON-GRID
terminal on the inverter, as shown in Fig. 55 below.
EQX2
SOLAR INVERTERS CONNECTED TO THE GRID
USER MANUAL
Содержание EQUINOX EQX2 3001-HSX
Страница 2: ...2 SALICRU...
Страница 51: ...51 ES EQX2 INVERSORES SOLARES DE CONEXI N A RED MANUAL DE USUARIO...
Страница 54: ...54 SALICRU...
Страница 103: ...103 EN EQX2 SOLAR INVERTERS CONNECTED TO THE GRID USER MANUAL...