11.1. „min_0V“ - {0ppm-2000} %, Pa

 

11.2. „max_10V“- {0ppm-2000} %, Pa

12. „CO2“ - when CO2 control is selected, min. and max. limits are set for the CO2 converter

 

12.1. „min_0V“ - {0ppm-2000} %, ppm

 

12.2. „max_10V“- {0ppm-2000} %, ppm

 

12.3. „PPM_100%“ - {20-255}*100ppm

13. „VentCtrl“ - setting of the indications for fans

 

13.1. „SAF“ - {Percent, Pressure} settings for the indications of the supply air motor %, Pa.

 

13.2. „EAF“ - {Percent, Pressure, SAF+Percent} settings for the indications of the extracted air motor %, Pa

 

 

 SAF+Percent – the alteration of the extracted motor can change only at set value according to the supply.

 

13.3. „CO2“- {On/Off} extracted air CO2 sensor

 

13.4. „ResetToFactorySettings“ - after switching “OK”, factory settings are saved. 

               NOTICE! The unit and the controller reloads.

14. „Misc“ - stop conditions for the unit depending on the connection of the controller

14.1. „RC NC“ - {On, Off}

 

On – ( Remote Control ) No controller, the unit is stopped

 

Off – ( Remote Control ) No controller, the unit is on

 

 

This setting is not applicable if the unit is controlled via ModBus interface.

14.2. „F Timer“ - {On, Off}

 

On – ( Filters timer ) filter contamination timer on. Item „Filters“ appears on the main menu of the user.

 

Off – ( Filters timer ) filter contamination timer off.

14.3. „AX“ - {0, 1}

 

0 – overheat protection NC

 

1 – contactor malfunction protection indication

14.4. „Fans On“ - {On, Off}

 

On –in case of „AX“ protection, fans work at maximum speed.

15. „AF“  - anti-frost security settings

15.1. „AF detect“- {Off, DewP/PlateT, Toutside, Tesetpoint, Klingb, Heatex}for choosing anti-frost security algorithm type.

 

DewP/PlateT – according to the dew point and the heat exchanger wall temperature calculation algorithm

 

Toutside – according to outdoor sensor (DIBT)

 

TEsetpoint – according to exhaust air sensor

 

Klingb – according to Klinberger (hexagon) heat exchanger anti-frost diagram.

 

Heatex – according to Heatex (quadrangular) heat exchanger anti-frost diagram.

15.2. „FanReduc.“  - {On, Off} supply fan speed deceleration

 

On –allowed

 

Off – forbidden

15.3. „Bypp/Rot“- {On, Off}on activation of anti-frost protection. 

 

On –possible to open the bypass valve o to stop the rotor. 

 

Off –impossible to open bypass valve or stop the rotor.

 

15.4. „PassiveTC“ - {Off, 16,5°C}alarm report supplying low temperature air according to time set in 15.5.

 

15.5. „Excercise“   - {Off, 1-12h}how much time it is possible to supply low temperature air till the alarm report.

 

Off – only when temperature falls till „PassiveTC“ (see.:15.4).

16. „AF1“ –Anti-frost protection settings

 

Selecting 15.1. „AF detect“ - „DewP/PlateT“

 

16.1. „PlateTemp“ - 1°C – {-5 +10 °C}heat exchanger humidity temperature

 

Selecting 15.1. „AF detect“ - „Toutside“

 

16.1. „OutDoorTemp“ -

 

Selecting 15.1. „AF detect“ -  „Tesetpoint“

 

16.1. „ExhaustTemp“ - {-20 +15 °C}when exhaust air temperature falls below the set value - anti-frost protection starts according to exhaust 

air temperature.

 

16.2. „RotorPWM“ – rotor impulse width modulation percentage. 

 

16.3. „DefrStpTime“ – rotor standing/defrosting time in minutes.

 

16.4. „PassiveTemp“ – outdoor air temperature value, in case of exceeding which, anti-frost function is allowed.

17. „CONF1“ - (only from V2.3 controllers‘ versions)

 

17.1. „CONF1“ - {„Ver X.2“, “Ver X.3“}

 

 

“Ver X.3“ – for turning on „DIBT“ and „Passive house“ functions.

 

 

It is possible to choose „Building protection“ unit‘s working mode,

 

 

No speed choice „Stop“, ( at „Schedules“ as well)

 

 

Necessary to set „Menu“ → „Extra“ → “Service” → “Menu configuration”

 

 

Necessary to set „Menu“ → „Menu configuration“ →  „Economic temper.“

 

17,2 „3dayRH mean“ –for setting three-day humidity average %

 

17,3 „3dayRHCurr“ – three-day average of humidity %

 

17,4 „3dayOUTCurr“ - three-day average of outdoor air °C

 

17.5. „St/Sp time“ - External timer delay time for unit‘s switch to another mode.

18. „CONF2“ - (for controllers with V2.4.1. and higher)

 

18.1. „Old RC compatib“ - {*On“, „Off“} – compatibility with older remote controllers.

 

 

„On“ – the controller works with  UNI, PRO, TPC and FLEX remote controllers but doesn‘t support extended ModBus address list.

 

 

„Off“ – controller works with FLEX remote controller and supports extended ModBus address list. 

 

18.2. „empty1“ - unused

 

18.3.„empty2“ - unused

 

18.4. „empty3“ - unused

 

18.5.„empty4“ - unused

Содержание Smarty 3X VER

Страница 1: ...Subject to technical modification AHU WITH HEAT RECOVERY Smarty 3X VER Smarty 3X VEL Smarty 3X VER 3 0 Smarty 3X VEL 3 0 User s and service technical manual...

Страница 2: ...ter mode setting 24 10 Comfortable supply air temperature 25 11 Night cooling 25 12 Heat cool recovery 25 13 Fast button stand by mode 26 14 Filter timer 28 15 Boost fireplace function 29 16 Bypass da...

Страница 3: ...s includes 1 Siphon 1 pcs 2 Key 1pcs 3 Anti vibration mounts 4 pcs 4 Anti vibration rubber 2 pcs 5 Mounting bracket 1 pcs 200003025238 IV PV KE PE M 0 084 kW 0 92 A 230 50 V Hz 1 0 085 kW 0 93 A 230 5...

Страница 4: ...79 2013 Extract panel M5 WxHxD 435 x 175 x 25 mm Supply panel F7 WxHxD 435 x 175 x 25 mm Outdoor exploitation temperature 5 C to 40 C Not suitable for swimming pools saunas and other similar facilitie...

Страница 5: ...onment Do not use the unit if external connections are broken or damaged If there are any defects stop operating the unit and replace the damaged parts immediately That can be performed only by qualif...

Страница 6: ...for the life of the motor Detach fan from the unit Impeller should be specially checked for buil up material or dirt which may cause an imbalance Excessive imbalance can lead to accelerated wear on m...

Страница 7: ...7 Smarty 3X VE Smarty 3X VE 3 0 www salda lt Smarty 3X VEL Smarty 3X VEL 3 0...

Страница 8: ...to have been damaged in transit a claim should be made against carrier as we assume no responsibility for such damage 3 This warranty does not apply 3 1 when transportation storage installation and m...

Страница 9: ...urrent kW A 0 3 1 3 control input ON OFF Pre heater EKA NIS phase voltage 1 230 power current kW A 1 0 4 3 control input 0 10 V Smarty 3X VER Smarty 3X VER 3 0 Smarty 3X VEL Smarty 3X VEL 3 0 Smarty 3...

Страница 10: ...3X VE Smarty 3X VE 3 0 www salda lt 750 500 162 113 113 372 160 150 6 150 6 233 8 113 113 372 160 150 6 150 6 233 8 750 500 162 598 943 Smarty 3X VER Smarty 3X VER 3 0 598 943 Smarty 3X VEL Smarty 3X...

Страница 11: ...evel of noise caused by the fans is admissible The installation is recommended at the distance of 400 mm from the nearest wall If it is not possible the installation of the unit is recommended on the...

Страница 12: ...control panel technical manual Stretch the connection cable which is included into standard package between the control panel and control box The cable of the control panel can t be stretched togethe...

Страница 13: ...twork connection place RS485_1 Control panel connection place PC Personal computer MBGateway Net module Flex Control panel Stouch Control panel M2 Fresh air damper actuator Recommended to use with ret...

Страница 14: ...amper ZAKP0027 TF230 Spring return actuator for damper ZAKP0063 MPL Panel filter set GKOFILSMARTY3 FLEX Remote control panel PRGPU015 Stouch Remote control panel PRGPU051 S KCO2 CO2 sensor ZAKKT0049 E...

Страница 15: ...the temperature reaches 3 C anti frost protection stars to work Pre heater EKA NIS for anti frost protection has to be ordered additionally The pre heater has overheat protection protection limiting t...

Страница 16: ...heating or accidental oxygen burning The electrical supply air heater is controlled according to the PID controller on the basis of the on off control principle When the unit is switched off the heati...

Страница 17: ...fan operation mode can be used where prompt indoor air changes are required at the increase of air pollution e g if the number of people in a room quickly increases The fan speed in this case is incre...

Страница 18: ...u Additional Service password Vent Control off Where the CO2 transmitter is used by Stouch remote control In the remote control Flex select Menu Additional Service password Vent Control The parameter...

Страница 19: ...xtra SAF Ctrl SAF low Where Stouch remote control is used all settings made by Flex remote control become inactive All settings of this function must be made by Stouch remote control Time can be confi...

Страница 20: ...s supply and extract air it is necessary to use two pressure transmitters 1141 They are ordered individually Pressure transmitters are used only when connected by Flex remote control The use of forced...

Страница 21: ...ding its proper connection Connection of a functional node to a ventilation unit To use this function the short circuiter must be removed from terminals 5 and 6 its installation is standard 5 6 PIR bu...

Страница 22: ...Supply air actuator M3 phase L1 steady signal 20 Supply air actuator M3 phase L1 control variable signal Actuator supply voltage 230V 50Hz When the water cooler is used we recommend to connect the spr...

Страница 23: ...F permit can be active by means of the unit shut down function Where the supply air temperature drops below 16 5 C the unit control automation records it as the minimum permissible supply air temperat...

Страница 24: ...time meter is activated in the service menu Menu additional sevice FMisc Ftimer Function adjustment setting By FLEX remote control Menu Extra filters Set Timer service hours until the information mess...

Страница 25: ...n the unit s technical decal on the unit casing The unit must be connected to the voltage plug socket of the grounded power network in compliance with the effective requirements The unit must be earth...

Страница 26: ...tretching The standard length of the unit s power cable is 2 5 m long from the unit casing The supply air sensor SS must be installed as far from the unit as the sensor cable enables or to the first b...

Страница 27: ...Fig 4 5 When the unit control automation must be extended from the automation compartment the limiting automation extension screw must be unscrewed and two connectors of the automation must be disconn...

Страница 28: ...installed in the extract air duct Tool for drilling holes are required for its installation CO 2 concentration ppm 3000 Effect on an individual 2500 2000 Reduced concentration drowsi ness headache et...

Страница 29: ...ation is stopped if the device has rotor heat exchanger In the remote controller temperatures the set and the measured are displayed as degrees Celsius C Room air temperature can be adjusted not only...

Страница 30: ...of the FLEX description If water supply air heater is used and after HVAC unit is switched on fans are switched on after 20 seconds During this period water valve actuator is being opened to allow wat...

Страница 31: ...perature sensor for supply air TJK 10K TE exhaust air damper actuator TJK 10K DTJ100 1 temp and humidity sensor for extract air PV supply air fan EC IV extract air fan EC FA fire alarm input B1 units...

Страница 32: ...System alarm 1 2W max 4 5 6 10 9 X16 4 24 1 2W max System on 11 12 COM FAN 25 24 23 24V DC 24 intput 0 10V DC 25 GND Transmitter 1 24 VDC P 23 X29 X25 N L 3 1 P DX Cooling A 0 10 COM 14 11 G M5 24VAC...

Страница 33: ...System alarm 1 2W max 4 5 6 10 9 X16 4 24 1 2W max System on 11 12 COM FAN 25 24 23 24V DC 24 intput 0 10V DC 25 GND Transmitter 1 24 VDC P 23 X29 X25 N L 3 1 P DX Cooling A 0 10 COM 14 11 G M5 24VAC...

Страница 34: ...5 3 2 NO 1 COM 6 7 8 L X31 X33 15 X33 16 COM A 0 10 X41 1 X41 2 X39 2 X39 1 X38 1 X38 2 X40 3 X40 2 X40 1 X34 8 X34 7 X34 6 X34 5 X34 4 X34 3 X34 2 X34 1 X33 26 X33 25 X33 17 X33 12 X33 18 X33 14 X33...

Страница 35: ...5 3 2 NO 1 COM 6 7 8 L X31 X33 15 X33 16 COM A 0 10 X41 1 X41 2 X39 2 X39 1 X38 1 X38 2 X40 3 X40 2 X40 1 X34 8 X34 7 X34 6 X34 5 X34 4 X34 3 X34 2 X34 1 X33 26 X33 25 X33 17 X33 12 X33 18 X33 14 X33...

Страница 36: ...l applicable safety and functional requirements diameters etc earthing and protection systems are properly installed condition of all seals and sealing surfaces is proper The recuperator can be connec...

Страница 37: ...ir temperature set 0 30 17 RH_value 04h_Read_Input 13 1 DTJ 100 humidity sensor value 0 99 18 Motor1 04h_Read_Input 15 1 Motor1 fan speed value 0 3 19 Motor2 04h_Read_Input 16 1 Motor2 fan speed value...

Страница 38: ...temperature limit day T is exceeded for the working unit and when temperature drops below Night T and the room temperature stays above Room T after switching the unit off 8 1 Day T 15 40 C maximum ou...

Страница 39: ...pply fan speed deceleration On allowed Off forbidden 15 3 Bypp Rot On Off on activation of anti frost protection On possible to open the bypass valve o to stop the rotor Off impossible to open bypass...

Страница 40: ...vel is exceeded the information message High CO2 level is displayed at the initial screen and the speed of fans is increased based on the amount at which allowable level is exceeded 5 In case of any f...

Страница 41: ...selected Bypass 0 10 Not used Cooling X16 4 X16 8 NO contact closed non voltage X16 1 X16 3 Activated by remote control V LED4 atidaroma X16 2 X16 3 Deactivated by remote control LED5 u daroma Heatin...

Страница 42: ...Fire input A1 A1 Fire alarm activation Extract humidity X40 Extract air humidity sensor readings Supply air temp X39 Supply air temperature sensor failure Extract air temp X38 Extract air temperature...

Страница 43: ...Always Seasons Exit Switch season Exit 3 days mean v Calendar Summer Winter Settings Exit Outdor air temp 0 C Summer 4MM 1DD Winter 11MM 1DD PI Kp 10 Ki 8 RoomPI Kp 100 Ki 10 HeatPI Kp 30 Ki 10 ChilP...

Страница 44: ...imer On AX 1 FansOn On AF AF detect Toutside FanReduct Off Bypp Rot Off PassiveTC Off Exercise AF 1 OutDoorTemp 1 RotorPWM 20 DefrStpTime 30 PassiveTemp 3 CONF1 3dayRH mean 30 3dayRHCurr 54 3dayOUTCur...

Страница 45: ...t EAF 1 SAF Ctrl SAF Low 0 3 SAF Midd 0 6 SAF High 1 EAF Ctrl EAF Low 0 3 EAF Midd 0 6 EAF High 1 SERVICE PI Kp 10 Ki 8 RoomPI Kp 100 Ki 10 HeatPI Kp 30 Ki 10 Byp RotPI Kp 10 Ki 10 ChilPI Kp 10 Ki 10...

Страница 46: ...SAF High 100 VentCtrl SAF Percent EAF Percent CO2 Off Misc RC_NC Off F Timer On AX 0 FansOn On AF AF detect Klingb FanReduct On Bypp Rot On PassiveTC Off Exercise AF 1 RotorPWM 20 DefrStpTime 30 Passi...

Страница 47: ...reccuperation Calculating main PID value between Tset and Tsupply to determinate what type of ventilation we need ByPass CLOSE ByPass OPEN ByPass OPEN Toutside Troom ByPass OPEN Cold reccuperation Tou...

Страница 48: ...48 Smarty 3X VE Smarty 3X VE 3 0 www salda lt...

Страница 49: ...50Hz delay of 3 minutes after stopping fans and heaters O 3A 100 X35 5 EXT L damper motor ON OFF 230V 50Hz O 3A 100 X3 RS485_2 ModBus I O X4 RS485_1 Remote controller FLEX I O X32 1 LOW Electrical hea...

Страница 50: ...itter DTJ100 1 DTJ100 1 Relative humidity transmitter has a built in NTC10K temperature sensor TA 3250 3300K Relative humidity transmitter supply voltage 5VDC Used current not higher than 5 mA Output...

Страница 51: ...inigung Once a year Einmal im Jahr Filter replacement Filter Ersatz Every 3 4 months 3 4 Alle 3 4 Monate NOTE The purchaser is required to fill in the Product maintenance table HINWEIS Der K ufer ist...

Страница 52: ...52 Smarty 3X VE Smarty 3X VE 3 0 www salda lt...

Отзывы: