background image

28

RIS 1200VE/VW EKO 3.0

X33

26

COM

COM

-

-

-

X34

1

A1

Priešgaisrinė apsauga

Brand Alarm

Fire guard

Feuerschutz

DI

-

-

X34

2

A1

COM

-

-

-

X34

3

A2

Papildoma šilumokaičio apsauga

Varmeveksler Alarm

Additional heate exchanger guard 

Wärmetauscher-Zusatzschutz

DI

-

-

X34

4

A2

COM

-

-

-

X34

5

A3

Filtrų užterštumo apsauga

Filter Alarm

Filter guard

Filter-Schmutzschutz

DI

-

-

X34

6

A3

COM

-

-

-

X34

7

A4

Ventiliatorių apsauga

Ventilator Alarm

Fans guard

Fans guard

DI

-

-

X34

8

A4

COM

-

-

-

DTJ

100

Ištraukiamo oro dregmės ir temeperatūros jutiklis.

Temperatur og fugtighedsmåler udsugning

Temp. and humidity sensor for extract air.

Abluftfeuchte- und Temperaturfühler.

X38

1

Ištrukiamo oro temperatūros jutiklis

Udsugning temperatur sensor

Extract air temperature sensor 

Abzugsluft-Temperatursensor

AI

-

-

X38

2

COM

-

-

-

X40

1

+5V

-

-

-

X40

2

Ištraukiamo oro santykinės dregmės jutiklis

Udsugning fugt sensor

Extract air humidyti sensor 

Abluft-Feuchtigkeitssensor

AI

-

-

X40

3

COM

-

-

-

TJ

Tiekiamo oro temperatūros jutiklis.

Indblæsningsføler

Supply air temperature sensor.

Temperatursensor der Zuluft.

X39

1

Tiekiamo oro temperatūros jutiklis

Indblæsnings sensor

Supply air temperature sensor 

Zuluft-Temperatursensor

AI

-

-

X39

2

COM

-

-

-

TE

Šalinamo oro temperatūros jutiklis

Afkastføler

Exhaust air temperature sensor 

Abluft-Feuchtigkeitssensor

X41

1

Šalinamo oro temperatūros jutiklis

Afkast temperatur sensor

Exhaust air temperature sensor 

Abluft-Feuchtigkeitssensor

AI

-

-

X41

2

COM

-

-

-

PV

Tiekiamo oro ventiliatorius.

Indblæsning ventilator

Supply air fan.

Ventilator der Zuluft.

X37

1

V1

Tiekiamo oro ventiliatorius 0-10V

Indblæsningsventilator 0-10V

Supply air fan 0-10V

Zuluft-Ventilator 0-10V

X37

2

COM

COM

-

-

-

IV

Ištraukiamo oro iš patalpos (-ų) ventiliatorius.

Udsugningsventilator

Extract room(s) air fan.

Ventilator der Abluft (aus dem Raum bzw. aus den Räumen).

X37

3

V2

Ištraukiamo oro ventiliatorius 0-10V

Udsugningsventilator 0-10V

Extract air fan 0-10V

Abluft-Ventilator 0-10V

X37

4

COM

COM

-

-

-

Содержание RIS 1200VE/VW EKO 3.0

Страница 1: ...Subject to technical modification Der tages forbehold for ndringer og rettelser RIS 1200VE VW EKO 3 0 Techninis vadovas lt Teknisk manual dk Technical manual en Bedienungsanleitung de REKUPERATORINIAI...

Страница 2: ...ngimo schema Kai elektrinis ildytuvas 30 Elektrinio jungimo schema Kai vandeninis ildytuvas 31 Gaminio prie i ros lentel 32 Indhold Transport og opbevaring 4 Beskrivelse 4 Sikkerhedsforanstaltninger 4...

Страница 3: ...ater 31 Product maintenance table 32 Inhalt Transport und Lagerung 4 Beschreibung 4 Schutzmassnahmen 4 Bestandeile des Ger tes 5 Betriebsbedingungen 5 Bedienung 6 Filter 6 Ventilator 6 W rmetauscher 6...

Страница 4: ...heater has cooled down and the restart is not possible Do not connect to any other power voltage source than indicated on the model label Use external motor protection switcher only corresponding to...

Страница 5: ...ben Die Anlage muss stabil montiert werden um einen sicheren Betrieb zu gew hrleisten Die Anlage darf nicht in explosionsgef hrdeter Umgebung oder f r aggressive Stoffe verwendet werden Verwenden Sie...

Страница 6: ...standen i filtret hvorefter mindre luft bl ses ind i lokalerne Det er tilr deligt at skifte filtre hver 3 4 m neder eller i overensstemmelse med signal fra filtervagten Sensor PS 600 er integreret i a...

Страница 7: ...se uheld misbrug bev gelige sliddele Vi kan ikke holdes ansvarlig for tilf ldige og f lgeskader regning og tab Garantien g lder heller ikke for udstyr hvor ndringer er blevet udf rt vores samtykke Dis...

Страница 8: ...ukimai hastighed speed Drehzahl min 1 3400 tiekimo indsugning supply zuluft galia srov str m power current Nennleistung Nennstrom kW A 0 430 2 95 apsisukimai hastighed speed Drehzahl min 1 3400 valdym...

Страница 9: ...L2 mm 46 Tiekimo indsugning supply Zuluft F7 Plotis Bredde Width Breite L mm 650 Auk tis H jde Height H he H mm 314 Gylis Dybde Depth Tiefe L2 mm 46 Filtro modelis Filter model Filter model Filter Mod...

Страница 10: ...air duct system the connection openings of ventilation system air ducts must be opened If necessary the maintenance side can be changed When connecting air ducts consider the air flow directions indi...

Страница 11: ...under 0 skal alle r r isoleres Dr nsystem skal installeres under anl gsh jde When AHU 1 is already placed the draining system has to be connected In order to do that the thimble or RIS 1200VE EKO 3 0...

Страница 12: ...or of by pass damper PS1 supply air differential pressure switch PS2 extract air differential pressure switch IV I traukiamo oro ventiliatorius PV tiekiamo oro ventiliatorius PR plok telinis ilumokait...

Страница 13: ...per SKG Schliessklappen SKG SP Sklend s pavara Spj ldmotor on off Actuator for dampers Klappenmotor KCO2 RC02 F2 RCO2 D F2 1141 SPs Spyruoklin sklend s pavara Spj ldmotor Spring back Spring return act...

Страница 14: ...Steuersignal M6 Stellantrieb des Wasserventils Tiekiamo oro temperat ra gali b ti reguliuo jama pagal tiekiamo arba i traukiamo oro tem perat ros jutiklio i matuot ir vartotojo nuotoli niame valdymo p...

Страница 15: ...algorithm of the extracted air sensor is selected then supply air temperature is adjusted based on estimated additional received heat heat emitted by the sun electric heaters etc Thus the energy for e...

Страница 16: ...ve actuator M6 is forced to open regardless the need for heat Second if the water temperature does not reach 10 C after fully opening the hater valve and the air temperature after heating drops below...

Страница 17: ...an be controlled using FLEX panel and BMS network simultaneously the device will work based on the latest changes of settings As set in the factory the device will operate if no faults are present bas...

Страница 18: ...Tiekiamo oro temperat ros jutiklio pavojaus signalas dk Indbl snings temperatur sensor alarm en Supply air temperature sensor alarm de Zuluft Temperatursensor Alarm 1 active o passive 9 RH 01h_Read_C...

Страница 19: ...pajungimo kabel esant FLEX pultelio komplektacijoje tarp valdymo pulto ir VOK agregato Nuotolinio valdymo pultel rekomenduojama sumontuoti atskirai nuo j gos kabeli Pastaba Jei naudojate kabel kartu...

Страница 20: ...rature sensor M1 BYPASS damper actuator 24VDC 0 10VDC M2 outside air damper actuator 230VAC M3 extract air damper actuator 230VAC M5 water cooler valve actuator 24VAC 3 position FA fire alarm input PS...

Страница 21: ...ary to ensure the accuracy of measurement Antifreeze protection When external supply air water heater is used it is necessary to prop erly install antifreeze protection from possible freezing of heat...

Страница 22: ...al connections of the unit St rung in elektrischen Verbindungen Anschl s sen des Aggregats lt Patikrinti jung i lizdus ir ki tukus sitikinti ar sujungiamieji kontaktai nepa eisti dk Tjek soklen og sti...

Страница 23: ...niert Tiekiamo PV arba i traukiamo IV oro ventiliato riaus gedimas Indbl sning PV eller udsugning IV ventilator fejl Supply PV or extracted IV air fan fault St rung des Ventilators f r Zuluft PV oder...

Страница 24: ...ratur v re h jere end tempera turen p termostaten Skal st p 5 kontakt skal v re lukket mellem terminal 4 og 1 Fig 2a Check on indbl sningsluften er lavere end termostaten hvis ja skal der motorventil...

Страница 25: ...25 RIS 1200VE VW EKO 3 0...

Страница 26: ...ktrisk forvarmer Rotor On off 230V 50Hz Electric preheater rotor ON OFF 230V 50Hz Elektrovorheizer Rotor EIN AUS 230V 50Hz O 16A 100 X12 Esamo grei io ventiliatoriaus tampa Sp nding ventilator normal...

Страница 27: ...CHIL DX au inimas ON OFF 24V DX k ling ON OFF 24V DX cooling ON OFF 24V DX K hlung EIN AUS 24V DO 0 05mA X33 10 COM COM X33 11 ALARM Indikacija sugedus ventiliatoriui iams ON OFF 24V Vises n r der er...

Страница 28: ...air humidyti sensor Abluft Feuchtigkeitssensor AI X40 3 COM TJ Tiekiamo oro temperat ros jutiklis Indbl sningsf ler Supply air temperature sensor Temperatursensor der Zuluft X39 1 Tiekiamo oro tempera...

Страница 29: ...is shipped in good working order and condition We therefore extend to the original purchasers the following Warranty for the period of two years from the original date of purchase If equipment is fou...

Страница 30: ...DC 28 GND Transmitter 2 24 VDC P 28 27 26 X33 22 X33 21 COM T set 4 X16 2 PS3 1 2 HR A4 A4 PUMP AC N L N V1 COM X12 X42 X37 2 X37 1 COM V2 X37 3 X37 4 X4 X3 ModBus RTU RS485_2 RS485_2 A1 A1 A2 A2 A3 A...

Страница 31: ...RTU X3 X4 X37 4 X37 3 V2 COM X37 1 X37 2 X42 X12 COM V1 N L AC N PUMP A4 A4 HR 2 1 PS3 X16 2 15 16 E1 0 10V in PE N L K1 11 K1 14 IV GND E1 0 10V in X34 L2 L1 N PE L1 L2 L3 N PE 1 2 3 4 5 6 7 8 9 9 8...

Страница 32: ...filtre Filter replacement Filter Ersatz Kas 3 4 m nesius Hver 3 4 m ned Every 3 4 months Alle 3 4 Monate PASTABA Produkt sigij s asmuo privalo pildyti Gaminio prie i ros lentel Produkt checkiste skal...

Отзывы: