EN |
11
KUB T120_KUB EKO v2019.04
ECODESIGN DATA TABLE
KUB EKO
100-630
50-355
67-400
67-500
80-560
80-630
Declared typology
Unidirec-
tional
Type of drive
Variable
Type of HRS
N/A
N/A
N/A
N/A
N/A
N/A
Nominal NRVU flow rate
[ m3/s ]
2,89
0,47
0,83
1,41
1,66
2,57
Effective electric power input
[ kW ]
2,9
0,41
0,79
1,27
1,52
2,98
SFPint
[ W/(m3/s) ]
N/A
N/A
N/A
N/A
N/A
N/A
Face velocity
[ m/s ] 0
0
0
0
0
0
Normal external pressure
[ Pa ]
580
422
493
448
494
600
Internal pressure drop of ventilation compo-
nents
[ Pa ]
N/A
N/A
N/A
N/A
N/A
N/A
Static efficiency of fans used in accordance
with Regulation No 327/2011
[ % ] 57,8
48,4
52,1
49,7
54
51,8
Declared maximum external leakage
[ % ] <1
<1
<1
<1
<1
<1
Casing sound power level (Lwa)
[ dB(A) ] 76
57
59
62
67
73
ErP Compliance
2018
2018
2018
2018
2018
2018
Internet address for disassembly instructions
www.salda lt