![Sakura FCA 201 Скачать руководство пользователя страница 27](http://html.mh-extra.com/html/sakura/fca-201/fca-201_technical-manual_801563027.webp)
Page
2
6
c) Install an expansion tank at the highest position as shown in the diagram.
The capacity of the expansion tank is 0.03~0.034 of the water volume.
d) Install 60 mesh Strainer to ensure the water quality is good.
e) Ensure the flow switch is installed and function properly.
f) Ensure all water pipes are well insulated
g) Fill up water after water piping work complete. Check the water leakage at
connections and joints.
5) Entering and leaving water temperature sensor installation
a) Loading and unloading of the compressor is controlled by master unit
based on leaving and entering water temperature.
b) The entering and leaving water temperature sensor are connecting to the
TH4 and TH5 of the master unit. The standard wire length for both sensors
is 4 meters.
c) Insert the sensor coil bracket and sensor into the water return and water
supply pipe as shown in the diagram:
Содержание FCA 201
Страница 1: ...Ref S FR 266 11 19 Models FCA 201 601 AIR COOLED MODULAR CHILLER ...
Страница 6: ...Page 5 Operating Range Cooling ...
Страница 7: ...System Schematic Diagram Page 6 Model FCA201 301 401 501 601 ...
Страница 17: ...Dimensions Page 16 Model FCA201 301 Model FCA401 ...
Страница 18: ...Page 17 Model FCA501 601 ...
Страница 25: ...Page 24 FCA201 301 401 501 601 Maintenance Maintenance ...