Page 13
3
.
Modbus Protocol Specification- Optional
For WP01V_BMS V1.0
3
.
1
Communication protocol
The way of start communication
:
After the order is sent from master to
slaver(WP01V_BMS), the communication is started
。
3
.
2
The structure of Communication data
(
a
)
Interface Communication style
:
RS485-2W
mode
:
RTU
(
Remote Terminal Unit
)
Synchronization mode
Connector type
:
Blue Color Connector Mark
A B
(
b
)
The bit rate
:
9600[bps]
(
c
)
The format of each datum:
Start bit: 1[bit]
Data bit: 8[bit]
Stop bit: 1[bit]
(
d
)
Coil, input mode, remain record, input record definition
(
e
)
Every one idu WP01V_BMS need a modbus unique ID, range from 1-16; Id 0
is use for broadcast Id
WP01V_BMS
SW1-4 Set Modbus Slaver ID
SW-1
SW-2 SW-3 SW-4
Modbus ID
0
0
0
0
1
1
0
0
0
2
0
1
0
0
3
1
1
0
0
4
0
0
1
0
5
1
0
1
0
6
0
1
1
0
7
1
1
1
0
8
0
0
0
1
9
1
0
0
1
10
0
1
0
1
11
1
1
0
1
12
0
0
1
1
13
1
0
1
1
14
0
1
1
1
15
1
1
1
1
16
(
f
)
Modbus Table Description 03 Function
Содержание FCA 201
Страница 1: ...Ref S FR 266 11 19 Models FCA 201 601 AIR COOLED MODULAR CHILLER ...
Страница 6: ...Page 5 Operating Range Cooling ...
Страница 7: ...System Schematic Diagram Page 6 Model FCA201 301 401 501 601 ...
Страница 17: ...Dimensions Page 16 Model FCA201 301 Model FCA401 ...
Страница 18: ...Page 17 Model FCA501 601 ...
Страница 25: ...Page 24 FCA201 301 401 501 601 Maintenance Maintenance ...