2.8 Operational Data Inquiry
Press and hold “SET” button for 5 seconds, this will enable operational data
inquiry, unit module number display area will show the 9 subs menu as listed in
the following table, while the temperature display area will show the
correspondent sub menu’s operational data. Press” SET” button to select different
sub menu (1 to 9). To exit, press “CLEAR” button.
Sub
menu#
Operational Data
Unit
Acceptable Operational
Range and Default Value
1
Chilled Water Temperature
Setting
Ԩ
Chilled Water Setting:
Supply – 5 to 30, default: 7
Ԩ
Return – 7 to 30, default: 12
Ԩ
2
N/A
N/A
N/A
3
Compressor Minimum Running
Time
Minutes 1 to 10, default: 5 minutes
4
Compressor Minimum Idle Time Minutes 1 to 10, default: 4 minutes
5
Compressor Load Time Interval
Minutes 2 to 10, default: 3 minutes
6
Compressor Unload Time
Interval
Minutes 1 to 5, default: 1 minutes
7
N/A
N/A
N/A
8
N/A
N/A
N/A
9
N/A
N/A
N/A
10
Temperature Differential
Setting
Ԩ
1-5
Ԩ
, default: 2
Ԩ
Содержание FCA 201
Страница 1: ...Ref S FR 266 11 19 Models FCA 201 601 AIR COOLED MODULAR CHILLER ...
Страница 6: ...Page 5 Operating Range Cooling ...
Страница 7: ...System Schematic Diagram Page 6 Model FCA201 301 401 501 601 ...
Страница 17: ...Dimensions Page 16 Model FCA201 301 Model FCA401 ...
Страница 18: ...Page 17 Model FCA501 601 ...
Страница 25: ...Page 24 FCA201 301 401 501 601 Maintenance Maintenance ...