15

12.

Trouble Shooting.

Item

Problems

Possible Reasons

PCS Warning

Hardware failure

The possible reason:
The output is overloaded, or the output load is short-circuited, or
the battery is low-voltage protected, or the inverter is damaged.
Can try to restart it to check if it works normally.

PCS Over heated

The load is too heavy or the system is installed in somewhere with
high temperature and bad ventilation

AC voltage failure

The grid power is abnormal

Batter voltage failure

The battery voltage is too low or the battery is in low voltage
protection

The communication of PCS
with main control system

The main control system failed to communicate with PCS

MPPT Solar

Charger Failure

Battery voltage is low

No battery power, need be charged

Solar panel is over-current

Connect too much solar panel

PV input is over-voltage

Too much panel in series connection, and the PV input voltage
exceeds 150Vdc. Check if the solar panel connection and qty are
correct.

Controller is over
temperature

The solar panel power exceeds the max PV input power, or the
solar panel is installed in somewhere with high temperature and
poor ventilation

Lithium Battery

Protection

The LiFePO4 cell is
over-voltage protection

The internal cell is over charged. Just disconnect
charging, and discharge the battery with the load

The LiFePO4 cell is
low-voltage protection

No power in the battery. Need be charged in time or some
LiFePO4 cell is damaged.

The LiFePO4 pack is
over-voltage protection

The battery is over charged, just discharge the battery with the
load.

The LiFePO4 pack is
low-voltage protection

No battery power, need be charged in time

Over temperature
protection in charging

The set charge current is too big, or the product is installed in
somewhere with high temperature and poor ventilation

Low temperature protection
in charging

The ambient temperature is too low to charge

Over temperature
protection in discharging

Too much load or the product is installed in somewhere with high
temperature and poor ventilation

Low temperature protection
in discharging

The ambient temperature is too low to discharge

Over-current protection
In charging

The charging current setting is too high

Over-current protection
In discharging

Too much load

Short circuit protection

The load is too heavy or the battery is short-circuited or the
internal BMS is damaged

Содержание ESS-1KW

Страница 1: ...User Manual ESS 1KW Energy Storage System WIFI APP download page ftp smartree y66 dnsnd com WIFImonitor apk...

Страница 2: ...face 1 4 Product Features 1 5 Warranty Policy 2 6 Basic System Structure 2 7 Installation 3 7 8 WIFI Setting 7 10 9 System Wire Connection 11 13 10 Switching Operation Steps 13 14 11 Solar Panel Selec...

Страница 3: ...6 Be very cautious when working with metal tools on or around the energy storage system Dropping a tool may cause a spark or short circuit in batteries or other electrical parts even cause an explosio...

Страница 4: ...nsportation or other external force intrusion The transportation methods should be properly selected by the user and the seller just assist to send them to the shipment agent 4 Under the following cir...

Страница 5: ...onfirm the following points before installation Do not install the energy storage system on the flammable materials device Install the system on the solid surface to prevent falling off Install the en...

Страница 6: ...ts of expansion screws M6 60mm and 3 sets of screws KM5 10mm The screws must be fixed tightly to avoid falling off and hurt others Step 2 Place the energy storage system to hanging bracket Attention W...

Страница 7: ...nection ports 1 AC input over current reset breaker 2 AC input port 3 Reserve lithium battery balancing port If the internal lithium battery cells get unbalanced after years use they can be balanced v...

Страница 8: ...harging 3 The grid power grid is normal and in the input range 4 Work mode switch is selected to the grid connected mode Timing grid connection mode can be set via APP can set the start time of grid c...

Страница 9: ...mode and feeds power to grid the indicator keeps light 2 When it is on grid mode and in standby status it flashes every 3 seconds 3 When it is on grid mode and AC keeps charging it flashes every 0 5...

Страница 10: ...Set between 1 40A For example 20 0 means the charge current of 1st charging period is 20A This charging here refers to the mains charging instead of solar charging For solar charger it will be automat...

Страница 11: ...harge period The SOC will be compared with the discharge time whichever arrives first and it stops first For example SOC is set as 50 while the discharging feeding to grid time is set as 10 minutes Wh...

Страница 12: ...nd discharge period 20 0 Set between 1 20A For example 20 0 means the charge current of 2nd discharging period to grid is 20A This discharging here refers to battery power feeds to grid For example if...

Страница 13: ...f solar panel with energy storage system Caution Do not reverse connect the positive and negative poles of solar panel Be careful of electric shock 9 2 1 Place all connection wires at the back side of...

Страница 14: ...ed in the package to the AC input port of energy system Make sure all wires are fixed properly and tightly to avoid heating caused by loose or poor contact 9 3 3 Place all connection wires at the back...

Страница 15: ...nna to the energy storage system 10 Switching Operation Steps 10 1 Double check if all wires are connected correctly and tightly 10 2 After double confirmation turn on the battery breaker 10 3 Press t...

Страница 16: ...he grid power fails or is abnormal it needs work as off grid mode can connect small household loads to the AC output socket running in off grid mode 10 8 Turning off steps are reversed 11 Solar panel...

Страница 17: ...ed in somewhere with high temperature and poor ventilation Lithium Battery Protection The LiFePO4 cell is over voltage protection The internal cell is over charged Just disconnect charging and dischar...

Страница 18: ...les 25 1500cycles 45 Grid input Parameters 1 Max Power Feed to Grid 600W Max 2 AC Input Current 0 40A Adjustable 3 AC Input Range 90 265VAC 4 AC Input Frequency Range 50HZ 3HZ 5 THDI 3 6 Rectification...

Страница 19: ...grid mode grid tied mode and other functions Protection Functions 7 1 IP Level IP21 7 2 Protection Overcharge protection Over discharge protection Over current protection Short circuit protection Ove...