BURNER FLAME CONTROL
SERIES
page 4 di 6
DOUBLE ELECTRODE FLAME DETECTION
IN ACCORDANCE WITH STANDARD EN 298
1 2
ON
3 4 5 6 7 8
1 2
ON
3 4 5 6 7 8
1 2
ON
3 4 5 6 7 8
1 2
ON
3 4 5 6 7 8
On
it is possible to set some
functions and some values through 8
microswitches housed on the on-
board electronic board.
The basic configuration of
microswitches is all 0
TIMES SETTINGS .
Pre Purge Time setting
Pre Purge 5 sec
Pre Purge 1 sec
Pre Purge 8 sec
Pre Purge 10 sec
Pre Purge 20 sec
Pre Purge 30 sec
1
2
ON
3 4 5 6 7 8
Pre Purge 50 sec
1
2
ON
3 4 5 6 7 8
Pre Purge 70 sec
1
2
ON
3 4 5 6 7 8
Ignition Time setting
Ignition Time 5 sec
1
2
ON
3 4 5 6 7 8
Ignition Time 12 sec
1
2
ON
3 4 5 6 7 8
Safety Time loss of Flame
Safety Time
2 sec
1
2
ON
3 4 5 6 7 8
Safety Time
3 sec
1
2
ON
3 4 5 6 7 8
FUNCTIONS SETTINGS .
Attempt to re-ignite after loss of flame
Yes
No
Ignition/re-ignitio attemps numbers
N° 1
N° 3
Detection flame circuit 24h self check
Enabled
1
2
ON
3 4 5 6 7 8
Disabled
1
2
ON
3 4 5 6 7 8
Self check OK
Self check No flame detection
Self check No flame detection
1 2
ON
3 4 5 6 7 8
1
2
ON
3 4 5 6 7 8
1
2
ON
3 4 5 6 7 8
1
2
ON
3 4 5 6 7 8
1
2
ON
3 4 5 6 7 8
1
2
ON
3 4 5 6 7 8