BURNER FLAME CONTROL
SERIES
page 1 di 6
DOUBLE ELECTRODE FLAME DETECTION
IN ACCORDANCE WITH STANDARD EN 298
INSTRUCTIONS FOR USE .
Read carefully and preserve this use and
maintenance reference manual.
CONFORMITY .
The manufacturer declares that:
-
has been designed, realized and
tested
in
compliance
with
the
European Rule
EN298
relative to
“Control and safety automatic systems
for gas burners and gas appliances
with or without fan.
-
it also complies with the
requirements essential provisions set
out in the following Directives:
-
2006/42 together with the paragraphs
relevant of EN 746,
-
2014/35/EU together with the regulations
relevant,
-
2014/30/EU together with the regulations
relevant
information
relating
to
disturbances electromagnetic
- This device shall be integrated with a
valve-proving system according to
EN 1643:2022 that checking the
leakage during each burner cycle
- EMC emission requirements shall be
tested after the incorporation into the
equipment
APPLICATIONS .
flame control appliance directly
lights and controls intermittent gas
burners,
or rather burners that shall be
turned off at least once in the 24 hours.
The burner is checked by an ionization
electrode.
For grounded grids.
With a single restart due to flame put out.
can be applied directly to the burner
in industrial thermal processes for metals,
glass, ceramic, plastic, chemical, etc....,
where there is no need of a pre-ventilation
before turning it on.
Besides it can be applied on atmospheric
burners for general heating.
ATTENTION
Avoid presence of condensation inside
the box and on the card surface.
TECHNICAL SPECIFICATIONS .
- Data
relating
to
power
supply
characteristics (V ~ / Hz / W), working
temperature (° C), IP00 protection
class, discharge time (Ig T), safety
(Sc) and detection threshold ( Sens.),
See the applied label.
- Voltage supplied to the loads the
same to the supply voltage.
-
Detection with 2 electrodes, 1
electrode or UV lamp
- Possibility of using both electronic
and traditional ignition transformers.
- LED display: on, block, discharge and
detection.
- Alarm contact in exchange: closed
when in block, closed when in flame
detection.
ATTENTION!!!
Any
indication
and
operation
indicated in the present manual
shall be carried out only by
authorized and qualified personnel
in charge.
Improper and incorrect assembly,
adjustment, modification, use or
maintenance can cause serious
damages and accidents to persons
and things.
Read carefully the instructions
before installing the appliance. The
assembly shall be in compliance
with the regulations in force.
In order to prevent accidental
electrocutions it is recommended
you disconnect the electric current
before opening the appliance.
Before supplying power check the
value reported on the tag.